Key takeaways
- IEC 60617 marks switching devices with a qualifier at the fixed contact: a cross for a circuit breaker, a bar for a disconnector and a semicircle for a contactor.
- An IEC fuse is a rectangle with a line running its full length; IEEE 315 also accepts an S-shaped curve drawn between the two terminals.
- North American one-line diagrams label circuit breakers with IEEE C37.2 device number 52, thermal relays 49, and instantaneous and time overcurrent relays 50 and 51.
- Under IEC 60898-1 a Type C MCB trips magnetically between 5 and 10 times rated current, so a C16 needs at least 160 A fault current.
- A thermal overload relay is drawn with a stepped thermal element in each phase and auxiliary contacts numbered 95-96 normally closed and 97-98 normally open.
Quick answer: The circuit breaker symbol in IEEE 315 schematics is an open contact bridged by a curved arc, and on North American one-line diagrams often a small square marked 52. IEC 60617 draws a switch blade with a cross at the fixed contact. The fuse symbol is a rectangle with a line through it in IEC, and a rectangle or S-curve in IEEE practice.
Protective devices are the symbols that matter most on a drawing, because they decide what happens during a fault. A breaker drawn where a disconnector was intended, or a fuse-switch confused with a switch-fuse, can leave a circuit without the interrupting capacity it needs.
This guide is for engineers, electricians, panel builders and buyers who read schematics, one-line diagrams and electrical blueprint symbols for distribution and motor circuits. It covers fuse symbols, circuit breaker and MCB symbols, isolators and disconnectors, contactors and thermal overload relays, in both IEEE 315 and IEC 60617 forms, and explains the device numbers and markings that go with them.
What Does the Circuit Breaker Symbol Look Like?
A circuit breaker is a mechanical switching device that can make, carry and automatically interrupt currents under normal and fault conditions. Its symbol must therefore show both a switching contact and the protective function. Three drawing contexts use different forms.
| Context | How the breaker symbol is drawn | Standard / practice |
|---|---|---|
| IEEE schematic | Two terminal points with a curved arc (like a small bridge) drawn over the gap; multi-pole breakers linked by a dashed line | IEEE 315 / ANSI Y32.2 |
| North American one-line | Small square box, labeled 52 for AC power breakers; drawout units shown with chevrons on both sides | IEEE C37.2 device numbers |
| IEC schematic and single-line | Switch blade angled open, with a small cross (x) on the fixed contact | IEC 60617 |
| Panel schedules and plans | Text only: breaker rating and poles, e.g. 20A/1P | Project legend |
A breaker schematic symbol for a molded-case or air circuit breaker on an IEC drawing usually also shows the trip units connected to the blade by a dashed mechanical link, as described below for MCBs. The device designation identifies it: -Q1 under IEC 81346 conventions, or CB1 on many North American drawings.
For the physical types behind these symbols, from MCBs to vacuum breakers, see our circuit breaker types guide. For context on how breaker symbols sit among other circuit symbols, start with the electrical symbols chart.
MCB Electrical Symbol and Trip Unit Elements
The MCB circuit breaker symbol in IEC 60617 builds on the basic breaker symbol (blade with cross) and adds the trip elements:
- Thermal (overload) element: a small square containing a stepped or hooked line, the IEC qualifier for thermal effect.
- Magnetic (short-circuit) element: a small square containing a bold bar, or marked I>, representing the electromagnetic trip.
- Mechanical link: a dashed line from the trip elements to the blade, showing they operate the contact.
Single-line diagrams usually simplify this to the breaker symbol with a rating tag such as C16 1P 6 kA. The letter is the tripping curve per IEC 60898-1.
| Curve | Instantaneous trip range | Typical application |
|---|---|---|
| B | 3 to 5 × In | Resistive loads, long cable runs |
| C | 5 to 10 × In | General circuits, lighting, small motors |
| D | 10 to 20 × In | Transformers, motors with high inrush |
Worked example: does a C16 MCB clear an earth fault?
For automatic disconnection under IEC 60364-4-41, the fault current must reach the instantaneous trip value. For a C16:
Ia = 10 × 16 A = 160 A
On a 230 V TN system, the maximum earth fault loop impedance is:
Zs(max) = U0 / Ia = 230 V / 160 A ≈ 1.44 Ω
If the measured loop impedance at the furthest point is 1.1 Ω, the circuit qualifies; at 1.8 Ω it does not, and a B16 (230 / 80 ≈ 2.88 Ω), larger cable or RCD is needed. Selection rules are covered in the low voltage circuit breaker selection guide.
Fuse Symbol: Schematic, Circuit Diagram and Fusible Link
A fuse is a protective device whose element melts and opens the circuit when current exceeds a defined value for a defined time. The fuse schematic symbol is one of the simplest on any drawing, but there are several variants.
| Symbol | How it is drawn | Standard |
|---|---|---|
| Fuse, general | Rectangle with a straight line through its full length, connected at both ends | IEC 60617, also IEEE 315 |
| Fuse, alternative US | S-shaped curve (one cycle of a wave) between two terminals | IEEE 315, older US drawings |
| Fuse with striker | Fuse rectangle with a short line and dot at one end, linked to a switch by a dashed line | IEC 60617, MV fused switches |
| Fusible link | Fuse symbol, often labeled FL or with wire gauge, sometimes a short thin wire segment | Automotive and control practice |
| Cut out fuse (dropout) | Fuse symbol on a hinged blade, or fuse with a curved arrow showing it drops open | Utility one-line diagrams |
| Thermal fuse / thermal switch | Fuse or switch symbol with a thermal qualifier or temperature marking | Appliance and transformer protection |
In a circuit diagram with a fuse, the fuse is drawn in series with the protected conductor, normally on the supply side of the load and on the line conductor, not the neutral. IEC drawings label it -F1 with rating and utilization category, for example gG 32 A (general purpose) or aM 25 A (motor back-up). North American drawings use labels such as FU1, 30 A Class J.
An electronic fuse symbol on a PCB schematic is the same rectangle, labeled with current and sometimes with PTC for a resettable polymer device. For MV transformer protection, fuse ratings follow the guidance in our transformer fuse sizing guide.
Isolator Symbol, Disconnector Symbol and Fusible Disconnect
A disconnector (isolator) is a switching device that provides a visible or verified isolating gap in the open position but is not designed to interrupt load current. A switch-disconnector can make and break load current and also provides isolation. The symbols make these differences explicit.
- Disconnector symbol (IEC): switch blade with a short bar drawn perpendicular across the fixed contact end.
- Switch-disconnector (IEC): the disconnector bar combined with a small circle, the qualifier for load-break switching.
- Isolator electrical symbol (IEEE one-line): a hinged blade between two terminals, labeled 89 per IEEE C37.2, with notes for load-break or non-load-break.
- Fuse-switch-disconnector: the fuse rectangle drawn on the moving blade itself, meaning the fuse moves with the contact.
- Switch-disconnector-fuse (fusible disconnect symbol): a switch-disconnector symbol with a separate fuse in series.
Earthing switches are drawn as a disconnector connected to the earth symbol. Interlock relationships between a breaker, disconnector and earthing switch are often shown with dashed lines or interlock notes, and they matter a great deal in MV switchgear.
The electrical disconnect switch guide explains when a disconnect must be load-break rated and how NEC and IEC 60947-3 categories (AC-22, AC-23) apply.
Contactor Schematic Symbol and Thermal Overload Symbol
Motor circuits combine a contactor and an overload relay, sometimes with a fuse or motor-protective circuit breaker upstream. Contactor schematic symbols differ markedly between the two conventions.
| Element | IEC 60617 | NEMA / IEEE ladder practice |
|---|---|---|
| Contactor coil | Rectangle, terminals A1 and A2, tag -KM1 or -Q1 | Circle with letter M (or 1M, 2M) |
| Main power contact | Switch blade with a semicircle (D shape) at the fixed contact | Two parallel lines, labeled M, in the power circuit |
| Auxiliary NO contact | Blade, no qualifier, terminals 13-14 | Two parallel lines |
| Auxiliary NC contact | Blade on contact with stop, terminals 21-22 | Two parallel lines with a diagonal |
| Thermal overload element | Rectangle with stepped thermal symbol in each phase | Heater drawn as a looped or hooked line, labeled OL |
| Overload relay contact | NC 95-96, NO 97-98, linked by dashed line to the element | NC contact labeled OL in series with the coil |
The thermal overload switch symbol on a control schematic is therefore usually just the NC contact (95-96) in series with the contactor coil: when the overload element heats, the contact opens and drops out the coil. The overload relay symbol carries IEEE C37.2 device number 49 on protection drawings. The motor circuit symbol itself, a circle with M and 3~, is covered with start-stop ladder logic in the motor control symbols guide, and starter arrangements in the motor starter types guide.
Switch Symbols in Protective Circuits and Other Symbols You Will Meet
Protective drawings also contain plain switches and a few symbols that searchers often lump together with breakers.
- Symbol for a double pole switch: two switch blades side by side joined by a dashed line, showing they operate together. A two-pole breaker uses the same dashed link between two breaker symbols.
- Two way switch symbol (2-way): in UK and IEC usage, a single-pole changeover (SPDT) blade between two fixed contacts. In North America the same device is called a three-way switch.
- Closed circuit symbol: a switch blade drawn touching its fixed contact; schematics normally show devices in their de-energized, unoperated state, so a closed blade means a normally closed device.
- Circuit protector symbol: supplementary protectors under UL 1077 are drawn like breakers but labeled as supplementary, since they are not branch-circuit breakers.
- Electrical symbol for antenna: a vertical line topped by an inverted triangle or Y, seen on metering and communication sheets.
- Speaker electronic symbol: a small rectangle with a trapezoid flaring from one side, used on alarm and paging drawings.
Full switch, relay and contact families are in the switch and relay symbols guide.
Common IEEE C37.2 device numbers
| Number | Function |
|---|---|
| 52 | AC circuit breaker |
| 72 | DC circuit breaker |
| 89 | Line switch / disconnector |
| 49 | Thermal relay |
| 50 / 51 | Instantaneous / time overcurrent relay |
| 86 | Lockout relay |
| 87 | Differential protective relay |
Next Steps: Specifying Breakers and Switchgear From the Drawing
Every breaker and fuse symbol on a single-line diagram should carry enough data for a supplier to price and build it. Before issuing an RFQ:
- Give each breaker its type (ACB, MCCB, MCB, VCB), frame and trip rating, poles, breaking capacity (Icu/Ics or kAIC) and trip unit functions such as LSIG.
- For fuses, give voltage, current rating, utilization category or UL class, and breaking capacity.
- Mark disconnectors as load-break or off-load, and state interlocks with earthing switches.
- Specify fixed, plug-in or drawout construction, and the switchgear standard: IEC 61439 or IEC 62271-200, or UL/IEEE C37 for North America.
- Include the prospective short-circuit current at each bus so ratings can be checked.
MARS manufactures KYN28 metal-clad MV switchgear with vacuum breakers, SF6 ring main units and IEC 61439 LV switchboards (GGD, GCS, MNS) fitted with ACBs and MCCBs, and supplies drawings in IEC or ANSI convention. Explore the HV and LV switchgear range and send your single-line diagram through the quote request form.
Frequently asked questions
What is the symbol for a circuit breaker on a schematic?
On IEEE 315 schematics a circuit breaker is drawn as an open contact bridged by a curved arc, with multiple poles linked by a dashed line. On IEC 60617 schematics it is a switch blade with a small cross at the fixed contact. North American one-line diagrams often use a small square labeled 52.
What is the electrical symbol for a fuse?
The standard fuse symbol is a rectangle with a straight line running through its full length, used in IEC 60617 and accepted by IEEE 315. Older North American drawings may show a fuse as an S-shaped curve between two terminals. The fuse rating and type, such as gG 32 A or Class J 30 A, is written beside it.
What is the difference between an isolator symbol and a circuit breaker symbol?
In IEC 60617 both start from a switch blade, but a disconnector or isolator has a short perpendicular bar at the fixed contact, while a circuit breaker has a cross. The bar shows isolation capability only; the cross shows the ability to interrupt fault current. A switch-disconnector adds a small circle for load-break duty.
How is an MCB shown in a single line diagram?
An MCB is shown with the IEC circuit breaker symbol, a blade with a cross, often with thermal and magnetic trip elements linked by a dashed line. Single-line diagrams usually simplify this and add a tag such as C16 1P 6 kA, giving the trip curve, rated current, number of poles and breaking capacity.
What does the contactor symbol look like?
In IEC drawings a contactor coil is a rectangle with terminals A1 and A2, and its main contacts are switch blades with a semicircle at the fixed contact. In NEMA ladder diagrams the coil is a circle labeled M, and its contacts are two parallel lines, with a diagonal added for normally closed contacts.
What is the thermal overload symbol?
A thermal overload relay is drawn in the power circuit as a rectangle containing a stepped thermal element in each phase, or as a looped heater line in NEMA practice. In the control circuit it appears as a normally closed contact, terminals 95-96, in series with the contactor coil, which opens when the motor is overloaded.
Written and reviewed by the MARS application engineering team in Shanghai, who specify and test transformers, switchgear, substations and battery storage for projects in 40+ countries. Last updated .
Tags: circuit breaker symbol fuse symbol mcb circuit breaker symbol isolator symbol contactor electrical symbol