Key takeaways
- A duplex receptacle on US plans is a circle with two parallel lines through it, while a single receptacle uses one line and a triplex uses three.
- Split-wired or half-switched receptacles are usually shown as a duplex symbol with half the circle filled in, wired to a switch marked S.
- IEC 60617 shows a socket outlet as a semicircle; a horizontal line across the top indicates a protective earth contact, common on 230 V plans.
- NEC 220.14(I) assigns 180 VA per receptacle yoke in non-dwelling occupancies, so a 120 V 20 A circuit carries at most 13 receptacles.
- Text tags such as GFCI, WP, USB, IG and a circuit number beside the symbol carry as much information as the outlet symbol itself.
Quick answer: The standard outlet symbol on a North American floor plan is a small circle with two short parallel lines through it, representing a duplex receptacle. One line means a single receptacle, a half-filled circle usually means split-wired, a square around the symbol means a floor outlet, and letters such as GFCI or WP add details. IEC plans draw a socket outlet as a semicircle.
The receptacle layout is the part of an electrical plan that owners, architects and electricians argue about most, because it decides where every appliance, desk and machine can be plugged in. Reading it correctly means knowing a small set of outlet symbols and the text tags that modify them.
This guide is for designers, estimators, electricians and building owners reviewing architectural electrical plans. It covers the duplex receptacle symbol and its variants, special purpose and floor outlets, switch symbols that appear alongside them, IEC socket symbols used on international projects, and how receptacle counts feed panel and switchboard sizing. Work on any building wiring or service equipment must follow local code and be carried out by a licensed electrician.
What Does the Electrical Outlet Symbol Look Like?
An electrical outlet symbol is a plan mark showing the location and type of a receptacle, the device into which a plug is inserted. In North American architectural practice the base shape is a small circle, typically 1/8 to 3/16 inch across at plotted scale, drawn against the wall line where the device is mounted.
Short straight lines drawn through or across the circle indicate the number of receptacles on the device:
- One line: single (simplex) receptacle.
- Two parallel lines: duplex receptacle, the standard wall outlet.
- Three lines: triplex receptacle.
- Two lines crossed by two more, or two duplex symbols together: quadruplex (double duplex) outlet, depending on the legend.
The lines are typically drawn perpendicular to the wall, so the symbol reads correctly on any wall orientation. Mounting height is not shown by the symbol; it comes from a general note (for example 18 inches to center above finished floor) or a tag such as +42" for counter height.
These architectural electrical symbols descend from the withdrawn ANSI Y32.9 standard, and today each firm's legend defines them. They are not the same as schematic connector symbols, which describe the electrical contact itself rather than its location. For the wider family of plan symbols, see our electrical symbols chart, and for lighting outlets on the same sheets see the lighting and plan symbols guide.
Receptacle Symbol Chart: Duplex, Single, GFCI and More
The chart lists the electrical receptacle symbols most often found on residential and commercial floor plans in North America, with how each is drawn.
| Outlet type | How the symbol is drawn | Typical meaning |
|---|---|---|
| Single receptacle | Circle with one line through it | One 15 A or 20 A receptacle, often dedicated |
| Duplex receptacle | Circle with two parallel lines | Standard 125 V duplex wall outlet |
| Quadruplex receptacle | Two crossed pairs of lines, or two duplex symbols | Two duplex devices in a two-gang box |
| Split-wired duplex | Duplex symbol with half the circle filled | One half switched, one half always on |
| GFCI duplex | Duplex symbol tagged GFCI or GFI | Ground-fault protection at the device |
| Weatherproof receptacle | Duplex symbol tagged WP | Outdoor or wet location cover |
| Isolated ground receptacle | Duplex symbol tagged IG, sometimes with a triangle | Separate insulated grounding conductor |
| Special purpose outlet | Circle with a triangle or letters (DW, R, D, AC) | Dedicated appliance or 240 V outlet |
| Floor outlet | Receptacle symbol inside a square | Floor box receptacle |
| Ceiling receptacle | Duplex symbol detached from wall, tagged C or CLG | Ceiling-mounted for equipment or cord reels |
| USB combination | Duplex symbol tagged USB | Receptacle with USB charging ports |
A duplex receptacle outlet symbol on a kitchen counter is usually also tagged GFCI and may carry a height note. Where a symbol appears without tags, the general notes on the sheet define the default device rating, color and mounting height.
Special Purpose, Split-Wired and Floor Outlet Symbols
Special purpose outlet symbol
A special purpose outlet is a receptacle or connection dedicated to one appliance or with a non-standard rating, such as a 240 V range, dryer, welder or air conditioner. Plans commonly draw it as a circle containing a solid triangle, or a circle with letters identifying the load. A subscript or schedule reference gives the voltage, amperage and NEMA configuration, for example 14-50R for a 125/250 V 50 A range receptacle or 6-20R for a 250 V 20 A outlet. Because the shape varies between firms, the legend is the only reliable key.
Split wired receptacle symbol
A split-wired receptacle has the tab between its two brass terminals removed so each half can be fed separately: one half from a wall switch, the other permanently live, or each half from a different circuit. The symbol is a duplex circle with one half shaded. When the two halves are on different circuits sharing a neutral, NEC 210.4 requires a means that simultaneously disconnects all ungrounded conductors, typically a two-pole or handle-tied breaker.
Floor outlet symbol
A floor outlet symbol encloses the receptacle symbol in a square representing the floor box. Plans may combine it with data symbols (triangle) inside the same square for a combination floor box. Floor boxes must be listed for floor use, and a coordination note usually ties their position to furniture layouts.
Junction box electrical symbol
A junction box is drawn as a circle or square with the letter J. It shows a point where conductors are spliced or a fixed appliance is hard-wired, and it must remain accessible. See the junction box with cover guide for enclosure selection.
Symbol for Outlet and Switch: Reading Them Together
Outlets and switches appear on the same power or lighting plan, and the symbol for outlet and switch combinations shows how control is arranged. Switches on floor plans use the letter S with subscripts:
| Symbol | Device | Notes |
|---|---|---|
| S | Single-pole switch | Controls a load from one location |
| S2 | Double-pole switch | Opens both ungrounded conductors, e.g. 240 V loads |
| S3 | Three-way switch | Pair controls a load from two locations |
| S4 | Four-way switch | Inserted between two three-way switches for three or more locations |
| SD or S with D | Dimmer | Rating and load type in schedule |
| SOS or OS | Occupancy or vacancy sensor | Wall or ceiling mounted |
| SWP | Weatherproof switch | Outdoor locations |
| SK | Key-operated switch | Restricted operation |
A curved dashed line from the switch to the controlled outlet or luminaire shows the switching relationship. When a dashed line runs to a half-filled duplex symbol, the switch controls the switched half of a split-wired receptacle, a common arrangement in living rooms without ceiling lights.
The four way switch symbol (S4) never appears alone: on a correctly drawn plan it sits between two S3 symbols linked to the same load. The internal contact arrangement of three-way and four-way switches is explained in the switch and relay symbols guide.
IEC Socket Outlet and Plug Socket Symbols
On IEC projects and in countries using 230 V systems, the electrical socket outlet symbol follows IEC 60617 installation-plan conventions, which look very different from the North American circle.
- Socket outlet, general: a semicircle (an arc open toward the wall side) with a short line connecting it to the wall, representing a single socket.
- Socket outlet with protective earth contact: the same semicircle with a straight line drawn across the top of the arc, the most common socket on European plans.
- Multiple socket outlets: the semicircle with a number written beside it (for example 2 for a double socket), or several arcs drawn together.
- Socket outlet with switch: the semicircle with an added angled switch stroke.
- Socket outlet with isolating transformer: the semicircle combined with a small transformer symbol, used for shaver outlets.
In schematic and wiring diagrams, the plug socket symbol and connector symbol describe the contacts. IEC draws the female socket as an open semicircle or U and the male pin as a solid bar entering it; IEEE 315 uses an arrowhead for the male contact and a V or chevron for the female. An accessory power outlet in a vehicle or on equipment panels carries a pictogram defined by ISO 2575 or IEC 60417 rather than a plan symbol.
Projects with mixed teams should state which convention applies in the legend, since an IEC semicircle may be mistaken for a wall-mounted light on a North American plan.
How Receptacle Counts Drive Circuit and Panel Sizing
Every receptacle symbol on a plan becomes load on a branch circuit and, ultimately, on a panelboard or switchboard. For non-dwelling occupancies, NEC 220.14(I) assigns 180 VA per single or multiple receptacle on one yoke. In dwellings, general-use receptacles are already included in the general lighting load per square foot.
Worked example: receptacles per 20 A circuit
A 120 V, 20 A branch circuit in an office:
Circuit capacity = V × I = 120 V × 20 A = 2,400 VA
Receptacles = 2,400 VA / 180 VA = 13.3, so a maximum of 13 duplex receptacles
Many designers apply a lower practical limit, for example 8 to 10 per circuit, to leave headroom for real equipment loads. An office floor with 260 duplex receptacles at 180 VA each represents 260 × 180 = 46,800 VA of receptacle load before demand factors. NEC 220.44 allows the first 10 kVA at 100% and the remainder at 50%:
10,000 + (36,800 × 0.5) = 28,400 VA
That demand load is then entered on the panel schedule alongside lighting and equipment loads to size the panelboard and its feeder. For layout rules, NEC 210.52 sets dwelling receptacle spacing so no point along a wall line is more than 6 ft from a receptacle, and kitchen countertops are limited to 24 in from a receptacle. The electrical panel guide explains how branch circuits are grouped.
Next Steps: From Outlet Layouts to LV Distribution Equipment
Outlet symbols define the smallest loads in a building, but their totals set the size of the distribution equipment upstream. When a project moves from floor plans to equipment procurement:
- Compile receptacle, lighting and equipment loads per panel, with demand factors per NEC Article 220 or IEC 60364 practice.
- Group panelboards onto an LV switchboard or distribution board, defining incomer rating, busbar rating and short-circuit rating.
- Specify the form of internal separation, IP or NEMA enclosure rating and metering.
- For larger sites, size the supply transformer from the total demand plus growth margin.
MARS does not manufacture wiring devices or residential panels. We build IEC 61439 low-voltage switchboards (GGD, GCS and MNS types), MV switchgear and the distribution and compact substation transformers that feed commercial and industrial buildings. See the HV and LV switchgear range or the dry-type transformer range for indoor supply, and send your load schedule through the quote request form.
Frequently asked questions
What is the symbol for a duplex receptacle?
The duplex receptacle symbol on North American floor plans is a small circle with two short parallel lines drawn through it, placed against the wall where the outlet is mounted. Tags beside it add information, such as GFCI for ground-fault protection, WP for weatherproof, or a circuit number linking it to the panel schedule.
What does a half-filled outlet symbol mean?
A duplex outlet symbol with half the circle shaded usually indicates a split-wired receptacle, where one half is controlled by a wall switch and the other half is always live. A dashed line from a switch symbol to the outlet confirms the switched half. Some legends use the same mark for a fully switched receptacle, so check the legend.
What is the symbol for a 240 V outlet on a floor plan?
A 240 V outlet is usually shown as a special purpose outlet: a circle with a solid triangle or with letters such as R for range or D for dryer. The schedule or a tag gives the voltage, amperage and NEMA configuration, for example 14-30R or 6-50R. Because practice varies, the drawing legend defines the exact symbol.
How is a floor outlet shown on electrical plans?
A floor outlet is shown by drawing the receptacle symbol inside a square that represents the floor box. If the box also contains data or communications outlets, their symbols, usually triangles, are placed in the same square. Plans normally dimension floor boxes or tie them to furniture plans, since they cannot be moved easily later.
What does the IEC socket outlet symbol look like?
In IEC 60617 installation plans, a socket outlet is a semicircle connected to the wall by a short line. A straight line across the top of the semicircle indicates a protective earth contact. A number beside the symbol shows how many sockets are grouped, and an added angled stroke shows a switched socket outlet.
What is the four way switch symbol on a floor plan?
A four-way switch is shown as the letter S with subscript 4, written S4. It is always placed between two three-way switches, shown as S3, that control the same luminaires or outlets, allowing control from three or more locations. Dashed lines connect the switches to the loads they control.
Written and reviewed by the MARS application engineering team in Shanghai, who specify and test transformers, switchgear, substations and battery storage for projects in 40+ countries. Last updated .
Tags: outlet symbol electrical outlet symbol duplex receptacle symbol receptacle symbol electrical outlet symbol floor plan