Key takeaways
- IEC 61850 defines the data models, configuration language and communication services used in digital substations, including MMS, GOOSE and sampled values.
- IEC 61869-9 sets preferred sampling rates of 4,800 samples per second for protection and 14,400 for power quality, for both 50 and 60 Hz.
- A sampled value stream at 4,800 frames per second and about 160 bytes per frame uses roughly 6 Mbit/s, so sixteen streams approach a 100 Mbit/s link.
- Process bus networks need time synchronization to about 1 µs, normally IEEE 1588 Precision Time Protocol with the IEC/IEEE 61850-9-3 profile.
- Redundancy protocols PRP and HSR in IEC 62439-3 give zero recovery time, and IEC 62351 adds security for IEC 61850 communication.
Quick answer: A digital substation replaces most copper wiring between primary equipment and protection, control and metering devices with IEC 61850 Ethernet networks. Merging units digitize CT and VT signals into sampled values on a process bus, breaker status and trips travel as GOOSE messages, and the station bus links IEDs to SCADA. The result is less cabling, more data and safer, more testable protection.
In a conventional substation, every current transformer, voltage transformer, breaker auxiliary contact and trip coil is wired with copper cable to relay panels in a control building. A medium-sized transmission substation can contain hundreds of kilometers of control cable, each core a potential wiring error and each terminal a maintenance task. Digital substations move that signal exchange onto fiber-optic Ethernet.
This guide is for utility engineers, EPC contractors and industrial owners evaluating digital substation automation solutions. It explains the architecture, the role of IEC 61850 and its key parts, how process bus and merging units work, a bandwidth calculation, time synchronization, cybersecurity, a migration path for existing substations and what to include in an RFQ. For substation fundamentals first, see what a substation is.
What Is a Digital Substation?
A digital substation is a substation in which measurements, status signals and control commands between primary equipment and secondary systems are exchanged as digital messages over Ethernet, using the IEC 61850 standard, instead of as analog and binary signals over copper wires.
The concept is built on three levels:
- Process level: primary equipment such as breakers, disconnectors, transformers, instrument transformers and the devices that digitize their signals: merging units and breaker interface units (sometimes called intelligent terminals).
- Bay level: protection relays, bay controllers and meters, called intelligent electronic devices (IEDs), which subscribe to process data and publish trips and commands.
- Station level: station HMI, gateways to the control center, engineering workstations and historians.
Two networks link the levels. The process bus carries sampled values and GOOSE between the process and bay levels. The station bus carries MMS reporting, control and GOOSE between bay and station levels. Many substations described as "digital" today use only the station bus, with conventional copper wiring at the process level; full digital substations add the process bus. Both stages are legitimate steps, and the benefits grow as more of the copper is replaced. Our substation automation engineering guide covers station-bus systems in more depth.
Conventional vs Digital Substation: What Changes?
The table compares a conventional substation with a full digital substation using a process bus.
| Aspect | Conventional | Digital (process bus) |
|---|---|---|
| CT and VT signals | 1 A or 5 A and 100–120 V analog over copper | Sampled values over fiber from merging units |
| Trips and interlocks | Hardwired contacts and auxiliary relays | GOOSE messages with defined priorities |
| Control cabling | Large multicore cable network to the control building | Fiber pairs; copper mostly limited to the bay |
| CT open-circuit hazard | Present on long secondary runs | Removed from control building; secondary circuits short and local |
| Configuration | Wiring diagrams and relay settings | SCL files (SSD, SCD, ICD, CID) to IEC 61850-6 |
| Testing | Secondary injection on terminals | Simulation and test mode on network; isolation by software and test switches |
| Condition data | Limited, local | Rich, timestamped and available to asset management |
| Main risks | Wiring errors, cable damage | Network design, time sync dependency, cybersecurity, skills |
The shift also changes the lifecycle. Primary equipment such as power transformers and switchgear typically lasts 30–40 years or more, while IEDs and network devices are refreshed on shorter cycles. A well-designed digital substation isolates those cycles so electronics can be upgraded without rewiring primary equipment, often by keeping merging units close to the primary equipment and standardizing interfaces.
IEC 61850: The Standards Behind Digital Substations
IEC 61850 is a family of standards, not a single protocol. The parts most relevant to digital substation design are:
| Standard | Covers |
|---|---|
| IEC 61850-6 | Substation Configuration Language (SCL): SSD, SCD, ICD and CID files |
| IEC 61850-7-x | Information models: logical nodes such as XCBR (breaker) and PTOC (overcurrent) |
| IEC 61850-8-1 | MMS client-server communication and GOOSE messaging |
| IEC 61850-9-2 | Sampled values over Ethernet |
| IEC/IEEE 61850-9-3 | Precision Time Protocol profile for power utility automation |
| IEC 61850-10 | Conformance testing |
| IEC 61869-9 | Digital interface for instrument transformers, including sampling rates |
| IEC 61869-13 | Stand-alone merging units |
| IEC 62439-3 | PRP and HSR network redundancy |
| IEC 62351 | Security for power system communication, including IEC 61850 |
Interoperability depends on these documents being applied consistently. In practice, utilities write a profile that specifies which logical nodes, data sets, GOOSE priorities and VLANs to use, and require each IED supplier to provide ICD files that pass conformance testing. The system integrator combines them into a single SCD file, the master description of the substation's communications. Without that discipline, mixing devices from different suppliers is where most digital substation projects encounter delays.
Process Bus, Merging Units and Non-Conventional Instrument Transformers
A merging unit is a device that samples current and voltage signals from instrument transformers, time-stamps them against a common clock and publishes them as IEC 61850 sampled value streams. It can be fed in two ways:
- Conventional CTs and VTs: the merging unit is installed in a kiosk or in the switchgear bay, close to the instrument transformers, so secondary wiring is short. This is the most common approach and keeps proven primary equipment.
- Low-power instrument transformers (LPITs): Rogowski coils, low-power CTs or capacitive and resistive dividers to IEC 61869-10 and -11, whose small output signals go directly to a merging unit. Optical current transformers use light polarization in fiber. These sensors avoid saturation and reduce size and weight.
On the output side, breaker interface units convert GOOSE trip and close commands into coil currents and publish breaker and disconnector positions. Protection IEDs then need only fiber connections.
Sampling rates follow IEC 61869-9: 4,800 samples per second for general protection and measurement, and 14,400 for power quality, for both 50 Hz and 60 Hz systems. Earlier implementations used the 9-2LE guideline at 80 samples per cycle, which is 4,000 per second at 50 Hz and 4,800 at 60 Hz. The merging unit's accuracy class and the instrument transformer's class must together meet protection and metering requirements; see our high voltage current transformer guide for conventional CT classes.
Worked Example: Process Bus Bandwidth and Time Synchronization
Process bus networks carry continuous, high-rate traffic, so bandwidth and timing must be calculated, not assumed.
Bandwidth
Each sampled value stream carries one frame per sample, typically with four currents and four voltages plus quality flags. Assume a frame size of about 160 bytes on the wire, including Ethernet overhead.
- Frames per second at 4,800 samples/s: 4,800
- Bit rate per stream:
4,800 × 160 × 8 = 6.14 Mbit/s - For 16 merging units on one network segment:
16 × 6.14 = 98 Mbit/s
Sixteen streams would saturate a 100 Mbit/s link before GOOSE and management traffic are added. Designers therefore use 1 Gbit/s backbones, limit the number of streams per port, and use VLANs and multicast filtering so each IED receives only the streams it subscribes to. A busbar differential relay subscribing to 12 streams receives about 74 Mbit/s, so it needs a port and processor sized for that load.
Time synchronization
Protection functions that combine samples from different merging units, such as transformer or busbar differential, need samples aligned to within about 1 µs. A time error of 1 ms at 50 Hz is a phase error of 360° × 0.001 × 50 = 18°, enough to produce false differential current. Digital substations therefore use IEEE 1588 Precision Time Protocol with the IEC/IEEE 61850-9-3 profile, distributed through PTP-aware switches from redundant grandmaster clocks, typically locked to GNSS. Merging units must also handle loss of synchronization safely, flagging samples so protection blocks or switches to functions that do not need cross-bay alignment.
Network Redundancy and Cybersecurity
When trips and measurements travel over Ethernet, the network becomes part of the protection system and must be as reliable as the copper it replaces.
Redundancy
Standard Ethernet recovery protocols take milliseconds to seconds to reconverge, which is too slow for protection. IEC 62439-3 defines two zero-recovery-time methods:
- PRP (Parallel Redundancy Protocol): each device sends every frame over two independent networks; the receiver uses the first and discards the duplicate.
- HSR (High-availability Seamless Redundancy): devices form a ring and send frames in both directions.
Many designs combine PRP at the station bus with PRP or HSR on the process bus, plus duplicated protection (main 1 and main 2) on separate merging units and networks.
Cybersecurity
A digital substation increases the attack surface, so security must be designed in:
- Network segmentation with firewalls between substation zones and the corporate or control center networks, following IEC 62443 zone and conduit concepts.
- Role-based access control, strong authentication and logging on IEDs, per IEC 62351.
- Secure engineering workflow for SCL files, with configuration change control.
- Patch and vulnerability management over the life of the substation.
- Physical security of network cabinets and fiber routes.
Regulatory frameworks vary by country; in North America, NERC CIP standards apply to many transmission substations.
Digital Substation Services: Engineering, Testing and Migration
Digital substation services cover the whole lifecycle, and the engineering effort shifts from wiring design to system configuration. A practical migration path for a utility or industrial owner is:
- Define a standard: an IEC 61850 profile, naming conventions, VLAN and priority plan, time sync and redundancy architecture.
- Pilot a station bus in a new or refurbished substation, using GOOSE for interlocking and MMS for SCADA.
- Add process bus in selected bays, for example a transformer bay, with merging units on conventional CTs and VTs and parallel conventional protection for comparison.
- Build test capability: SV and GOOSE simulators, network analyzers and test procedures using IEC 61850 test mode and simulation flags.
- Run FAT on the integrated system, not only individual devices, with the final SCD file.
- Roll out to full digital substations, retaining conventional fallback only where the risk assessment requires it.
- Plan lifecycle support: firmware management, spares, cybersecurity updates and training.
Digital substations also unlock condition monitoring: transformer temperatures, tap changer data, breaker operating times and partial discharge sensors become network data rather than isolated gauges. That connects naturally to partial discharge monitoring and to fast protection such as an arc flash relay. For physical works, see our substation construction guide.
Next Steps: Specifying Primary Equipment for a Digital Substation
Digital secondary systems still depend on primary equipment that is designed to integrate with them. MARS supplies power transformers up to 110 kV class, compact and containerised substations, KYN28 metal-clad switchgear and ring main units. Defining the digital interfaces at the RFQ stage lets the primary equipment be built and tested for them.
In your specification, include:
- Whether the project uses station bus only or station bus plus process bus, and the IEC 61850 edition and profile.
- Instrument transformer type: conventional CTs and VTs with merging units, or low-power instrument transformers, with accuracy classes.
- Space and power supply for merging units and breaker interface units in switchgear bays or kiosks.
- Transformer monitoring signals required: winding and oil temperature, tap position, gas and pressure relays, and any online sensors.
- Time synchronization, redundancy and cybersecurity requirements that apply to any IEDs supplied with the equipment.
- FAT scope, including integration tests with the system integrator's SCD file.
Explore our transformer substations and power transformers, and request a quote with your single-line diagram and IEC 61850 requirements. Our substation protection engineering guide covers the protection functions the network must support.
Frequently asked questions
What is the difference between a digital substation and a conventional substation?
A conventional substation exchanges measurements and commands as analog currents, voltages and contact signals over copper cables. A digital substation exchanges them as IEC 61850 messages over fiber-optic Ethernet, using merging units for sampled values and GOOSE for trips and status, which cuts cabling and adds monitoring data.
What is a process bus in a digital substation?
The process bus is the Ethernet network between process-level devices, such as merging units and breaker interface units, and bay-level protection and control IEDs. It carries IEC 61850-9-2 sampled values and GOOSE messages, replacing the copper wiring of CT and VT secondaries and trip circuits.
What is a merging unit?
A merging unit samples current and voltage signals from conventional or low-power instrument transformers, time-stamps them using a synchronized clock and publishes them as IEC 61850 sampled value streams. Protection relays and meters subscribe to these streams over the process bus instead of being wired to CT and VT secondaries.
Why does a digital substation need precise time synchronization?
Functions such as differential protection compare samples from several merging units. If samples are misaligned, a phantom differential current appears. A 1 ms error at 50 Hz is an 18 degree phase shift, so process bus systems use IEEE 1588 Precision Time Protocol to align samples within about 1 µs.
Are digital substations secure?
They can be when security is designed in. Good practice includes network segmentation and firewalls following IEC 62443, authentication and logging per IEC 62351, controlled configuration of SCL files, patch management and physical protection of network equipment. Regulations such as NERC CIP apply to many transmission substations in North America.
Can an existing substation be converted to digital?
Yes, usually in stages. Owners often start by adding an IEC 61850 station bus during relay replacement, then install merging units next to existing CTs and VTs in selected bays. Primary equipment such as transformers and switchgear can usually remain, while secondary systems are replaced bay by bay.
Written and reviewed by the MARS application engineering team in Shanghai, who specify and test transformers, switchgear, substations and battery storage for projects in 40+ countries. Last updated .