Rectifier Transformer Guide: Pulse Design, Sizing & TRUs

Rectifier transformer with heavy copper busbars feeding rectifier cabinets in an electrolysis plant

Key takeaways

  • A six-pulse bridge gives no-load DC voltage Udi0 = 1.35 × VLL, so a 463 V valve winding produces about 625 V DC before commutation drop.
  • Transformer rating for a three-phase bridge is about 1.05 times the ideal DC power, Udi0 × Id, because of non-sinusoidal winding currents.
  • Characteristic harmonics are h = kp ± 1, so a 12-pulse system cancels the 5th and 7th and leaves the 11th, 13th, 23rd and 25th.
  • Two secondaries shifted 30°, such as Yy0 and Yd11, produce 12-pulse operation; 18- and 24-pulse use extended delta or zigzag phase shifts.
  • Rectifier transformers are covered by IEC 61378-1 for industrial applications and IEEE C57.18.10 for semiconductor power rectifier transformers.

Quick answer: A rectifier transformer is a transformer designed to feed a rectifier that converts AC to DC. Its secondary windings are phase-shifted, for example star and delta for 12-pulse operation, to cancel harmonics, and it is built for harmonic heating, DC-related stresses and high secondary currents. It is specified under IEC 61378-1 or IEEE C57.18.10 for electrolysis, traction, drives and DC furnaces.

Aluminium smelters, chlor-alkali plants, hydrogen electrolyzers, DC traction substations and large multi-pulse drives all have the same front end: a transformer feeding a diode or thyristor rectifier. That transformer looks like an ordinary power transformer from outside, but its windings, losses and short-circuit behaviour are shaped by the converter it serves.

This guide is for process, traction and drive engineers who need to specify a rectifier transformer or check a supplier's design. It covers the difference between a rectifier and a transformer, pulse configurations, the DC voltage and kVA formulas with a worked example, harmonic and loss considerations, and transformer rectifier units.

Rectifier vs Transformer: What Each Does

The rectifier vs transformer question is a common starting point. A transformer changes the magnitude of an AC voltage through electromagnetic induction and provides isolation; its output is still AC at the same frequency. A rectifier converts AC into DC using diodes or thyristors, and on its own does not change voltage level in any controlled way except through phase control.

FeatureTransformerRectifier
Input / outputAC to ACAC to DC
Operating principleMagnetic inductionSemiconductor switching
Voltage changeSet by turns ratioFixed ratio (diode) or phase-controlled (thyristor)
IsolationYes (two-winding)No
HarmonicsDoes not generate (except magnetising)Generates characteristic harmonics
Typical standardIEC 60076, IEEE C57.12.00IEC 60146 series for semiconductor converters

In practice the two are combined. The transformer matches the utility voltage to the DC voltage required, isolates the DC system, limits fault current through its impedance, and, by using multiple phase-shifted secondaries, makes the rectifier behave like a converter with more pulses, which reduces harmonics. That combined duty is why a rectifier transformer is treated as a special transformer type; see our overview of different types of transformers. Treating it as a standard unit with a nominal kVA margin is a frequent cause of overheating in service.

Pulse Number and Phase-Shifted Secondaries

The pulse number p is the number of DC output voltage pulses per AC cycle. A three-phase full-wave bridge is six-pulse. Higher pulse numbers come from feeding several bridges from secondaries that are phase-shifted relative to each other by 60° / (number of bridges).

ConfigurationSecondaries and shiftLowest characteristic harmonicsTypical application
6-pulseOne, any connection5, 7, 11, 13Small drives, chargers, electroplating
12-pulseTwo at 30°, e.g., y0 and d1111, 13, 23, 25Traction substations, electrolysis, large drives
18-pulseThree at 20° (e.g., −20°, 0°, +20°)17, 19, 35, 37Multi-pulse drives
24-pulseFour at 15°, or two 12-pulse units shifted ±7.5°23, 25, 47, 49Smelters, large electrolyzers

Characteristic harmonics follow h = k × p ± 1, with ideal magnitudes of roughly I1 / h. In a 12-pulse system the 5th and 7th harmonic currents from the star bridge are equal and opposite to those from the delta bridge when referred to the primary, so they cancel in the supply line while still flowing in each secondary winding.

Phase shifts other than 30° are achieved with extended delta, zigzag or polygon windings on the secondary, or with phase-shifting windings on the primary of each unit in a multi-transformer group. Our phase-shifting transformer guide and transformer vector groups explained show how these connections produce the required angles. Transformers with two or more secondaries are a specialised form of the three winding transformer, often with a split-winding arrangement to decouple the bridges.

Rectifier Transformer Sizing: DC Voltage and kVA

Sizing starts from the DC side. For a three-phase six-pulse bridge:

  • Ideal no-load DC voltage: Udi0 = 1.35 × Uv0, where Uv0 is the valve-side line-to-line RMS voltage.
  • Thyristor control: Ud = Udi0 × cos α − Udx − UT, where α is firing angle, Udx the commutation drop and UT device forward drops.
  • Commutation drop for a bridge: approximately Udx ≈ (ux / 2) × Udi0 at rated current, with ux the per-unit inductive short-circuit voltage of the transformer.
  • Valve-winding RMS current: Iv = 0.816 × Id per bridge.
  • Transformer rating: S ≈ 1.05 × Udi0 × Id per bridge (more exactly π/3).

Worked example: 12 MW electrolysis rectifier, 600 V DC, 20 kA. Two diode bridges in parallel, each 10 kA, fed from star and delta secondaries for 12-pulse operation. Transformer ux = 8%.

  1. Commutation drop: Ud / Udi0 ≈ 1 − 0.08 / 2 = 0.96. Ignoring device drops, Udi0 = 600 / 0.96 = 625 V.
  2. Valve-side voltage: Uv0 = 625 / 1.35 = 463 V line-to-line for each secondary.
  3. Valve-winding current: Iv = 0.816 × 10,000 = 8,160 A per secondary.
  4. Secondary rating: √3 × 463 × 8,160 ≈ 6.54 MVA each, which agrees with 1.047 × 625 × 10,000 = 6.54 MVA.
  5. Primary rating: about 13.1 MVA for both secondaries combined.

The real design adds margin for device drops, bus losses, tap range for process control and electrolyzer ageing, which raises DC voltage requirement over life. Because DC current is very high, secondary windings and busbars are often designed with many parallel conductors and the transformer and rectifier are placed close together.

Harmonics, Losses and Special Design Features

Rectifier transformers carry non-sinusoidal current, which changes their thermal design. Standards IEC 61378-1 and IEEE C57.18.10 specify how to calculate losses with the converter's harmonic spectrum, instead of the sinusoidal assumptions of IEC 60076 or IEEE C57.12.00.

  • Winding eddy losses rise roughly with the square of harmonic order times the square of harmonic current, so the 11th and 13th harmonics contribute disproportionately. This is the same physics as the K-factor concept used for LV dry-type transformers; see our K-factor transformer guide.
  • Stray losses in tank walls, clamps and high-current secondary bus structures increase with harmonic frequency and with the large magnetic fields around 10–100 kA conductors.
  • DC magnetisation can occur with asymmetrical firing or faults and pushes the core toward saturation; designs allow for it.
  • Short-circuit stress: a rectifier arm failure or DC bus fault produces large forces, so impedance and mechanical bracing are chosen with the converter's protection.
  • Interphase reactors or balancing windings may be used where bridges are paralleled.
  • Regulation: diode rectifiers need on-load tap changers, saturable reactors or a separate regulating transformer to control DC voltage; thyristor rectifiers control voltage through firing angle, at the cost of power factor.

Losses matter economically because electrolysis plants run continuously. Our transformer losses and total cost of ownership article shows how to capitalise them.

Applications of Rectifier Transformers

Rectifier duty spans very different scales:

  • Electrolysis: aluminium smelting, chlor-alkali, copper and zinc refining and water electrolysis for hydrogen. Characterised by high DC current, continuous duty and multi-pulse arrangements, often 24 to 48 pulses across several transformer-rectifier groups.
  • DC traction substations: 750 V, 1,500 V and 3,000 V DC for metro, tram and rail systems, commonly 12-pulse or 24-pulse diode rectifiers fed from MV. Load is cyclic with heavy short-time overloads, which the converter and traction standards address with defined duty classes that the transformer must be rated for.
  • Multi-pulse drives: 18- and 24-pulse front ends for MV drives, frequently using cast-resin or oil-filled drive isolation transformers with several secondaries.
  • DC arc furnaces and graphitising furnaces: very high currents with thyristor control.
  • Electroplating, battery charging and DC distribution for industrial processes; see our DC distribution panel guide.
  • HVDC converter transformers, a specialised class covered by IEC 61378-2, with DC voltage stress on valve windings.

Battery energy storage takes the reverse path: its power conversion system inverts DC to AC and typically connects through a step-up transformer, which also sees harmonic and DC-related stresses, though at lower levels with modern PWM converters.

What Is a Transformer Rectifier Unit (TRU)?

A transformer rectifier unit (TRU) is a packaged assembly of a transformer and a rectifier that converts an AC supply into a regulated or unregulated DC output in one unit. The term is used in several industries:

  • Aircraft: TRUs convert the 115/200 V, 400 Hz three-phase AC bus to 28 V DC for avionics and control systems, usually with 12-pulse or higher rectification for low ripple without large filters.
  • Rail traction: a transformer-rectifier set at a DC traction substation, fed from 10–35 kV AC.
  • Electrostatic precipitators: high-voltage TRUs produce tens of kilovolts DC to charge dust particles in flue gas cleaning.
  • Cathodic protection: small oil-cooled or air-cooled TRUs supply DC current to protect pipelines and tanks.

In each case, the transformer part sets voltage and isolation, and the rectifier converts to DC. Larger TRUs follow the same design rules discussed above: phase-shifted windings for pulse number, harmonic-aware loss calculation and short-circuit coordination between transformer impedance and rectifier protection.

Small TRUs are often supplied as complete packaged products with the transformer, rectifier, filtering and controls integrated. At industrial scale the transformer and rectifier usually come from different specialists, so one party must own the interface: secondary voltage tolerance, impedance, bus arrangement and protection.

Next Steps: Specifying and Sourcing

A rectifier transformer cannot be quoted correctly from kVA alone. Provide the transformer supplier and the converter supplier with the same data set:

  1. DC output: rated voltage range, current, overload duty class and load cycle.
  2. Converter type: diode or thyristor, bridge or other connection, pulse number and the phase shift required for each secondary.
  3. Supply: voltage, frequency, short-circuit level and harmonic limits at the point of common coupling (IEEE 519 or the utility's rules).
  4. Harmonic spectrum of the winding currents, from the converter designer, for loss calculation per IEC 61378-1 or IEEE C57.18.10.
  5. Impedance target per secondary and between secondaries, regulation method and tap range.
  6. Cooling, installation (indoor or outdoor), secondary bus arrangement and losses evaluation.

MARS manufactures oil-immersed power transformers up to 31,500 kVA and 110 kV class and cast-resin dry-type transformers, designed to IEC 60076 with ANSI/IEEE, GB and GOST variants. For converter-fed applications, send the data above and the engineering team will review whether the duty, harmonic loading and secondary arrangement can be met and propose a design. Routine tests are carried out on every unit, FAT is welcome, and typical lead time for power transformers is 60–90 days. Use the quote page to start.

Frequently asked questions

What is the difference between a rectifier and a transformer?

A transformer changes AC voltage from one level to another using magnetic induction and provides isolation, while a rectifier converts AC into DC using diodes or thyristors. They are often used together: the transformer sets the voltage and phase shift, and the rectifier produces the DC output. A rectifier transformer is a transformer designed specifically for that combined duty.

Why do rectifier transformers have two secondaries?

Two secondaries shifted by 30 degrees, typically one star and one delta, feed two six-pulse bridges to create a 12-pulse rectifier. The 5th and 7th harmonic currents of the two bridges cancel in the primary, reducing harmonic distortion on the supply and lowering DC ripple. More secondaries with smaller shifts give 18- or 24-pulse operation.

How do you calculate the DC output voltage of a rectifier transformer?

For a three-phase six-pulse bridge, ideal no-load DC voltage is 1.35 times the valve-side line-to-line RMS voltage. Subtract the commutation drop, roughly half the per-unit inductive impedance times Udi0, and semiconductor forward drops. For thyristor rectifiers multiply Udi0 by the cosine of the firing angle before subtracting these drops.

What standards apply to rectifier transformers?

IEC 61378-1 covers transformers for industrial applications, including rectifier and converter duty, and IEC 61378-2 covers HVDC converter transformers. In North America, IEEE C57.18.10 covers semiconductor power rectifier transformers. These standards define harmonic loss calculation, duty classes, testing and rating methods beyond the general IEC 60076 or IEEE C57.12.00 requirements.

What is a transformer rectifier unit used for?

A transformer rectifier unit converts an AC supply into DC in a single packaged assembly. Common uses include aircraft 28 V DC systems fed from 115/200 V, 400 Hz AC, DC traction substations, electrostatic precipitators, cathodic protection of pipelines and battery charging. The transformer sets voltage and isolation; the rectifier provides DC output.

Why are rectifier transformers rated higher than the DC power?

Rectifier winding currents are not sinusoidal; they are blocks of current with harmonic content. The RMS current, and therefore heating, is higher than for a sinusoidal current delivering the same power. For a three-phase bridge the transformer rating is about 1.05 times the ideal DC power, and harmonic eddy and stray losses add further to thermal design.

Written and reviewed by the MARS application engineering team in Shanghai, who specify and test transformers, switchgear, substations and battery storage for projects in 40+ countries. Last updated .