Switchgear & Substations

Electrical Abbreviations List: Drawings, Panels & Breakers

Low voltage switchboard breakers where electrical abbreviations appear on labels and panel schedules

Key takeaways

  • Breaker labels such as 400AF/320AT 65 kAIC give frame size, trip rating and interrupting rating, which must exceed the available fault current at that bus.
  • Panel abbreviations identify purpose: PP is a power panel, LP a lighting panel, RP a receptacle panel, DP a distribution panel and MDP the main distribution panel.
  • IEC breaker data uses Icu, Ics and Icw for short-circuit ratings, while North American labels use AIC or kAIC and SCCR for assemblies.
  • HVAC nameplates give MCA for conductor sizing and MOCP for the largest permitted overcurrent device, per the equipment listing.
  • Drawing notes such as AFF, TYP, NIC, ETR and EC change scope and dimensions, so they must be read with the same care as symbols.

Quick answer: Electrical abbreviations are short codes used on drawings, panel schedules, breaker labels and nameplates. Common examples: CB (circuit breaker), MCCB (molded case circuit breaker), AIC (amperes interrupting capacity), PP (power panel), LP (lighting panel), MDP (main distribution panel), ATS (automatic transfer switch), AFF (above finished floor) and NIC (not in contract). Always confirm meanings against the project legend.

Electrical documents compress a great deal of meaning into two to five letters. A note reading “ETR, RL 600 mm AFF, EC to extend HR to PP-2” is perfectly clear to an experienced electrician and impenetrable to almost everyone else. Misreading one abbreviation can change a scope of work, a breaker rating or a mounting height.

This electrical abbreviations list is for engineers, electricians, estimators, facility managers and buyers who work with drawings, panel schedules, breaker box labels and equipment nameplates. It groups abbreviations by where you meet them, gives IEC equivalents where North American and international practice differ, and decodes a few real-world labels. Work on panels and service equipment must follow local code and be done by a licensed electrician.

Abbreviation for Breaker: Circuit Breaker Abbreviations

Circuit breaker abbreviations describe the device type, its ratings and its accessories. The basic abbreviation for breaker is CB; on IEC drawings breakers are tagged -Q followed by a number.

AbbreviationMeaningNotes
CB / BKRCircuit breakerGeneric
MCBMiniature circuit breakerDIN-rail, IEC 60898-1 or IEC 60947-2
MCCBMolded case circuit breakerUL 489 or IEC 60947-2
ACBAir circuit breakerLV power breaker, often drawout
ICCB / LVPCBInsulated case / low-voltage power circuit breakerNorth American LV power breakers
VCBVacuum circuit breakerMV switchgear
GFCIGround-fault circuit interrupterPersonnel protection, about 5 mA trip in North America
AFCIArc-fault circuit interrupterDwelling branch circuits per NEC 210.12
GFPEGround-fault protection of equipmentRequired on certain large services per NEC 230.95
RCD / RCCB / RCBOResidual current device / without / with overcurrent protectionIEC equivalents of GFCI-type protection
AF / ATAmpere frame / ampere tripe.g. 250AF/200AT
AIC / kAICAmperes interrupting capacityMaximum fault current the breaker can interrupt
LSIGLong-time, short-time, instantaneous, groundElectronic trip unit functions
ST or SHTShunt tripRemote tripping coil
UVRUndervoltage releaseTrips on loss of voltage
AUX / ALAuxiliary contact / alarm (bell) contactStatus indication
MOMotor operatorRemote open and close

For the physical device types behind these codes, see the circuit breaker types guide; for the matching drawing symbols, see the circuit breaker and fuse symbols guide.

Breaker Box Abbreviations on Panel Directories

Breaker box abbreviations are the short labels written on panel directories and panel schedules to identify each circuit's load. They are not standardized, but these are widespread in North American practice:

LabelLoadLabelLoad
LTG / LTSLightingREC / RECEPTReceptacles
KITKitchenBATHBathroom
DWDishwasherDISPDisposal
MWMicrowaveREF / FRIGRefrigerator
WH / WTR HTRWater heaterDRYDryer
WASH / WWasherRNGRange
A/C / ACAir conditionerFURN / AHUFurnace / air handling unit
HPHeat pumpEVSE / EVElectric vehicle charger
SPR / SPSpare (breaker fitted)SPCSpace (no breaker)
GFCI / GFGFCI-protected circuitAFCI / CAFCIArc-fault protected circuit

NEC 408.4(A) requires each circuit to be legibly identified as to its clear, evident and specific purpose, so labels like “misc” or “general” are not acceptable. On commercial panel schedules, a circuit line usually also shows the load in VA, the breaker trip and poles, and the phase, such as 20A/1P, A, 1,440 VA, REC RM 104.

The panel schedule guide shows how these entries roll up into panel and feeder loads, and the electrical panel guide explains panel construction and ratings.

PP Panel Electrical Meaning and Other Equipment Abbreviations

On one-line diagrams and riser drawings, equipment is named with abbreviations that indicate its function. The PP panel electrical meaning is power panel: a panelboard serving power loads such as motors, HVAC equipment and receptacles, often at 480 V or 208 V three-phase.

AbbreviationEquipment
MSB / MDP / MDBMain switchboard / main distribution panel / main distribution board
SWBDSwitchboard
SWGRSwitchgear
PP / PNLPower panel / panel
LPLighting panel
RPReceptacle panel
DPDistribution panel
ELP / EPPEmergency lighting panel / emergency power panel
MCCMotor control center
ATS / MTSAutomatic / manual transfer switch
UPSUninterruptible power supply
VFD / VSDVariable frequency / speed drive
XFMR / TX / TRTransformer
RMURing main unit
AIS / GISAir-insulated / gas-insulated switchgear or substation
CT / VT (PT)Current transformer / voltage (potential) transformer
BESS / PCSBattery energy storage system / power conversion system
GENGenerator
DISC / DSDisconnect switch

A panel name usually combines the type with a number and sometimes voltage or floor, for example PP-2A or LP-3H (H for 480Y/277 V, L for 208Y/120 V in many firms' conventions). The switchboard vs panelboard guide explains where the boundaries between these equipment classes lie. Transformer-specific abbreviations such as ONAN, BIL and HV/LV are listed in the transformer abbreviation guide.

Electrical Drawing and Specification Abbreviations

Drawing notes use abbreviations that affect scope, dimensions and materials. These are among the most frequently misread electrical acronyms.

AbbreviationMeaning
AFF / AFGAbove finished floor / above finished grade
TYPTypical: applies to all similar locations
NICNot in contract
EC / GC / MCElectrical / general / mechanical contractor
ETR / RL / RMExisting to remain / relocate / remove
(E) / (N) / (F)Existing / new / future
HRHome run to panel
JB / J-BOXJunction box
WP / WRWeatherproof / weather-resistant
EMEmergency
IGIsolated ground
EMT / IMC / RMC (GRC)Electrical metallic tubing / intermediate metal conduit / rigid metal (galvanized rigid) conduit
PVC / ENT / LFMCRigid PVC conduit / electrical nonmetallic tubing / liquidtight flexible metal conduit
MC / ACMetal-clad cable / armored cable (context distinguishes from mechanical contractor)
THHN / THWN / XHHWInsulated conductor types per NEC Table 310.4(A)
AWG / kcmilAmerican wire gauge / thousand circular mils
EGC / GECEquipment grounding conductor / grounding electrode conductor
C / COConduit / conduit only

Abbreviations with two meanings, MC and AC being the classic cases, are resolved by context and the legend. When reading a full drawing set, check the abbreviation list on the legend sheet before relying on any of these; our guide on how to read electrical drawings covers where legends and general notes sit in a typical set.

Electrical Engineering Abbreviations: Ratings and Quantities

Equipment data sheets and nameplates use an engineering vocabulary that differs between North American and IEC documents.

AbbreviationMeaningTypical use
V, kV / A, kAVolts, kilovolts / amperes, kiloamperesAll ratings
kVA / kW / kvarApparent / real / reactive powerTransformers, loads, capacitors
PFPower factorLoads, generators
FLA / FLCFull-load amps / full-load currentMotors
LRALocked-rotor ampsMotor starting
MCA / MOCPMinimum circuit ampacity / maximum overcurrent protectionHVAC nameplates
SCCRShort-circuit current ratingPanels and assemblies, NEC 409 and 440
BILBasic impulse insulation levelTransformers, switchgear
%ZPercent impedanceTransformers, fault calculations
THDTotal harmonic distortionPower quality
VDVoltage dropCable sizing
Ue / Ui / UimpRated operational / insulation / impulse withstand voltageIEC 60947 devices
In / IrRated current / long-time settingIEC breakers
Icu / Ics / IcwUltimate / service breaking capacity / short-time withstandIEC 60947-2 breakers
IP / NEMAIngress protection (IEC 60529) / NEMA 250 enclosure typeEnclosures

A North American kAIC rating and an IEC Icu rating express similar ideas but come from different test standards, so they are not directly interchangeable on a specification. Assembly-level ratings, SCCR in North America and the rated conditional or short-time currents under IEC 61439, depend on the combination of devices and busbars, not on the weakest breaker label alone.

Worked Example: Decoding Breaker and Nameplate Labels

Abbreviations become useful when you can turn a label into a design check.

Label 1: switchboard feeder breaker

MCCB 3P 400AF/320AT 65 kAIC @ 480 V, LSI, ST, AUX

  • Three-pole molded case breaker, 400 A frame, 320 A trip setting.
  • Interrupting rating 65 kA at 480 V.
  • Electronic trip with long-time, short-time and instantaneous functions; no ground-fault function.
  • Fitted with shunt trip and auxiliary contacts.

If the fault study gives 42 kA at that switchboard bus, the 65 kA rating is adequate: 65 kA ≥ 42 kA. A standard (80%-rated) breaker carries continuous load up to 80% of its trip rating:

Maximum continuous load = 0.80 × 320 A = 256 A

A 100%-rated breaker in a listed assembly could carry the full 320 A continuously. How the 42 kA figure is obtained is explained in the fault current calculation guide.

Label 2: rooftop HVAC unit nameplate

208/230V 3Ø 60 Hz, MCA 28.5 A, MOCP 45 A

  • Branch conductors must have ampacity of at least 28.5 A, so 10 AWG copper at a 30 A rating is typical, subject to terminal temperature and conditions of use.
  • The overcurrent device may not exceed 45 A; a 40 A or 45 A breaker is acceptable, a 50 A breaker is not.

Both checks follow directly from reading the abbreviations correctly, which is why they belong on panel schedules and submittals.

Next Steps: Using Clear Abbreviations in Switchgear Specifications

Ambiguous abbreviations in an RFQ produce ambiguous quotations. When specifying switchboards, switchgear or substations:

  • Include an abbreviation list with the specification and drawings, defining every code used.
  • Use full ratings with units: Icu 50 kA at 415 V or 65 kAIC at 480 V, not just “50k”.
  • State the standard each rating refers to: IEC 61439, IEC 62271-200, UL 891 or IEEE C37.20.2.
  • Use consistent equipment tags across single-line, schedules and nameplates.
  • Specify the nameplate and label language and content required on each device.

MARS supplies IEC 61439 LV boards (GGD, GCS, MNS), KYN28 metal-clad switchgear and SF6 ring main units with nameplates and drawings labeled to your tagging convention. Explore the HV and LV switchgear range and send your specification through the quote request form.

Frequently asked questions

What is the abbreviation for breaker?

The common abbreviation for breaker is CB, short for circuit breaker, or BKR on some drawings. More specific abbreviations identify the type: MCB for miniature, MCCB for molded case, ACB for air and VCB for vacuum circuit breakers. On IEC drawings breakers are tagged -Q followed by a number, such as -Q1.

What does PP mean on an electrical panel?

PP on an electrical panel or drawing means power panel, a panelboard that supplies power loads such as motors, HVAC units, receptacles and equipment, as distinct from an LP lighting panel. The name is usually followed by a number and sometimes a floor or voltage code, for example PP-2A or PP-1H.

What does AIC mean on a circuit breaker?

AIC stands for amperes interrupting capacity, often written kAIC in thousands of amperes. It is the maximum short-circuit current the breaker can safely interrupt at a stated voltage, such as 22 kAIC at 240 V. The rating must be equal to or greater than the available fault current where the breaker is installed.

What does AFF mean on electrical drawings?

AFF means above finished floor. It gives the mounting height of a device measured from the finished floor surface to the center or bottom of the device, as stated in the general notes. For example, 18 in AFF for receptacles or 48 in AFF for switches. AFG means above finished grade for outdoor equipment.

What does LSIG mean on a breaker trip unit?

LSIG describes the protection functions of an electronic trip unit: L for long-time overload, S for short-time delay, I for instantaneous and G for ground fault. A trip unit labeled LSI has the first three functions but no ground-fault protection. Each function has its own pickup and delay settings.

What is the difference between MCA and MOCP?

MCA, minimum circuit ampacity, is the smallest conductor ampacity allowed for the equipment's supply circuit. MOCP, maximum overcurrent protection, is the largest fuse or breaker rating permitted by the equipment listing. Both appear on HVAC and refrigeration nameplates, and the installed conductor and breaker must satisfy both values.

Written and reviewed by the MARS application engineering team in Shanghai, who specify and test transformers, switchgear, substations and battery storage for projects in 40+ countries. Last updated .

Tags: electrical abbreviations electrical abbreviations list circuit breaker abbreviations breaker box abbreviations electrical engineering abbreviations list

More guides

Printed panel schedule sheets and spreadsheet on an electrical engineer's desk
· 9 min read · Switchgear & Substations

Panel Schedule Guide: Templates, Examples & Load Totals

Panel schedule guide: what an electrical panel schedule contains, single and three phase layouts, a worked sample with phase totals and an Excel template setup.