Key takeaways
- IEC 60038 sets 230/400 V as the preferred low-voltage system for 50 Hz countries, with a tolerance of plus or minus 10 percent at the supply terminals.
- The UK and EU both declare 230 V nominal at 50 Hz, although the UK historically ran at 240 V and the continent at 220 V.
- India supplies 230 V single-phase and 400 to 415 V three-phase at 50 Hz, with 11 kV and 33 kV as the main distribution voltages.
- Canada uses 120/240 V for homes and 347/600 V three-phase for many commercial and industrial buildings, all at 60 Hz.
- A transformer designed for 60 Hz must not be run at full voltage on 50 Hz, because core flux rises by 20 percent and causes overheating.
Quick answer: Voltage by country falls into two families. Most of the world uses 220 to 240 V single-phase at 50 Hz, including the EU and UK (230 V), India (230 V) and China (220 V). North America uses 120/240 V at 60 Hz, with Canada adding 347/600 V. Exceptions include Japan (100 V, 50/60 Hz) and the Philippines (230 V, 60 Hz).
Exporting electrical equipment, building a plant abroad or moving a production line between continents all start with the same question: what voltage and frequency does the destination grid supply? The answer covers more than the wall outlet. Three-phase low-voltage and medium-voltage distribution levels decide which transformer, switchgear and motor ratings will work.
This reference gives verified nominal values for the markets buyers ask about most, explains the standards behind them, and shows how to translate country data into a correct transformer specification. It is written for project engineers, EPC contractors and equipment importers.
Voltage by Country: Reference Table of Mains and Three-Phase Supply
The table lists nominal low-voltage supply for common project markets. Values are the declared nominal; actual voltage varies within the national tolerance band.
| Country | Single-phase | Three-phase LV | Frequency | Typical MV distribution |
|---|---|---|---|---|
| United States | 120 / 240 V split-phase | 208Y/120, 480Y/277 V | 60 Hz | 12.47, 13.2, 13.8, 34.5 kV |
| Canada | 120 / 240 V split-phase | 208Y/120, 600Y/347 V | 60 Hz | 12.47, 13.8, 25 kV |
| United Kingdom | 230 V | 400 V | 50 Hz | 11 kV, 33 kV |
| EU (Germany, France, Netherlands etc.) | 230 V | 400 V | 50 Hz | 10, 20 kV (country dependent) |
| India | 230 V | 400 / 415 V | 50 Hz | 11 kV, 33 kV |
| China | 220 V | 380 V | 50 Hz | 10 kV, 35 kV |
| Philippines | 230 V (often quoted as 220 V) | Varies by utility | 60 Hz | Varies by utility |
| Malaysia | 230 V | 400 V | 50 Hz | 11 kV, 33 kV |
| Japan | 100 V | 200 V | 50 Hz east, 60 Hz west | 6.6 kV |
| Brazil | 127 V or 220 V by region | 220 or 380 V | 60 Hz | 13.8 kV |
| Ghana | 230 V | 400 V | 50 Hz | 11 kV, 33 kV |
| Uganda | 240 V | 415 V | 50 Hz | 11 kV, 33 kV |
Medium-voltage levels vary by utility within a country; always confirm with the local distribution company before finalizing a transformer primary rating. For the US in depth, see our US voltage standards guide.
What Is EU Voltage? Europe Standard Voltage and Frequency
EU voltage is 230 V single-phase and 400 V three-phase at 50 Hz. This was harmonized through IEC 60038 and the European standard EN 50160, which describes supply voltage characteristics at the customer terminals.
Before harmonization, continental Europe used 220/380 V and the UK used 240/415 V. Rather than rebuild networks, regulators set a common nominal of 230/400 V with tolerance bands wide enough to include both legacy systems. EN 50160 requires 10-minute mean RMS voltage to stay within ±10 percent of 230 V (207 to 253 V) for 95 percent of each week.
- Germany, France, Spain, Italy: 230/400 V, 50 Hz, with MV distribution commonly at 10 kV or 20 kV.
- Netherlands (Holland): electricity voltage in the Netherlands is 230/400 V, 50 Hz, with 10 kV the most common distribution level.
- Nordic countries: 230/400 V, 50 Hz, with some IT (unearthed) LV systems in Norway at 230 V line-to-line.
Power in Europe is delivered mainly through TN-C-S and TT earthing systems. A typical home has single-phase 230 V service, but three-phase 400 V household connections are common in Germany, Austria and the Netherlands, feeding cookers, heat pumps and EV chargers of 11 kW or 22 kW.
The single-phase behavior of 230 V circuits, including current and cable sizing, is covered in the 230V single-phase power guide.
What Is the Voltage in the UK? British Voltage Standard
The voltage in the UK is 230 V single-phase and 400 V three-phase at 50 Hz. The legal tolerance under the Electricity Safety, Quality and Continuity Regulations is +10 percent / -6 percent, giving 216.2 to 253 V. Because many networks were built for 240 V, measured voltage in England and the rest of Great Britain is often 240 to 245 V.
British electricity voltage reaches homes as single-phase 230 V from an 11 kV/400 V ground-mounted or pole-mounted distribution transformer. The LV network is a three-phase four-wire 400/230 V system, and each house is connected to one phase. Commercial premises take a three-phase supply.
| Level | UK nominal | Typical use |
|---|---|---|
| LV | 230 / 400 V | Homes, shops, small industry |
| MV distribution | 11 kV, 6.6 kV (some) | Secondary substations |
| Subtransmission | 33 kV, 66 kV, 132 kV | Primary substations, large industry |
| Transmission | 275 kV, 400 kV | National grid |
US vs UK voltage: the UK outlet supplies 230 V line-to-neutral at 50 Hz, almost double the US 120 V at 60 Hz. For the same power, UK circuits carry about half the current, which is why a standard UK ring final circuit runs at 32 A while US kitchens need multiple 20 A circuits. Moving appliances between the two needs a step-up or step-down transformer and a frequency check; see 110 volts to 220 transformer sizing.
India Voltage and Frequency: What Indian Power Supply Looks Like
India electricity voltage is 230 V single-phase and 400 V three-phase at 50 Hz, although 415 V is still widely quoted for three-phase because older equipment and tariffs used 240/415 V. National supply regulations allow a tolerance band around nominal, commonly cited as ±6 percent at LV.
Indian power voltage structure is distinctive in its heavy use of 11 kV and 33 kV distribution:
- 11 kV/433 V distribution transformers supply LV feeders. The 433 V open-circuit secondary allows for regulation so loads see roughly 400 to 415 V.
- 33 kV feeds primary substations and larger industrial consumers.
- 66 kV, 132 kV, 220 kV and 400 kV form subtransmission and transmission.
Agricultural pumping loads and long rural lines make voltage fluctuation a real design issue. Transformers for Indian service are commonly specified with off-circuit taps of ±5 percent in 2.5 percent steps, or on-load tap changers on larger units, and with energy efficiency levels set by BIS star ratings.
Voltage in India vs USA: India runs at 230 V 50 Hz, the US at 120/240 V 60 Hz. A 60 Hz US motor run in India at rated voltage will run about 17 percent slower and the motor core will see about 20 percent more flux, so it must either be rated 50/60 Hz or be run at reduced voltage (V/f constant). The physics are explained in the 50 Hz vs 60 Hz guide.
Canada Voltage: Is Canada 240V? 120/240 and 347/600 V
Canada voltage follows North American practice for homes: 120/240 V split-phase at 60 Hz. So yes, Canada has 240 V for ranges, dryers and baseboard heaters, but standard outlets are 120 V on NEMA-style receptacles.
The difference from the US is in commercial and industrial buildings. Canada power voltage for these facilities is commonly 600Y/347 V three-phase, a system almost unused south of the border.
- 347 V line-to-neutral supplies lighting.
- 600 V line-to-line supplies motors (nameplate 575 V), HVAC and process loads.
- Dry-type step-down transformers convert 600 V to 208Y/120 V or 120/240 V for receptacles.
For the same load, 600 V carries 20 percent less current than 480 V, reducing feeder copper. Electricity in Canada is governed by the Canadian Electrical Code (CSA C22.1), and equipment must carry CSA or equivalent certification rather than only UL listing.
Distribution primaries in Canada include 4.16 kV, 12.47 kV, 13.8 kV and 25 kV, with 25 kV common in newer suburban networks. Transformers for Canadian utilities often follow the CSA C802 efficiency standards and the CSA C227 series alongside IEEE dimensions.
Philippines, China, Malaysia and Other Asian Grid Voltages
Asia mixes 50 Hz and 60 Hz systems, and several countries carry legacy voltages.
Philippines voltage
Electric voltage in the Philippines is 230 V (commonly referred to as 220 V) single-phase at 60 Hz, an unusual combination inherited from US-era infrastructure. Distribution primary voltages vary by utility, so confirm the MV level and the earthing arrangement of the LV service before specifying protection.
Electrical voltage in China
China uses 220 V single-phase and 380 V three-phase at 50 Hz, with 10 kV the dominant MV distribution level and 35 kV, 110 kV and 220 kV above it. Transformer standards are GB 1094 (aligned with IEC 60076).
Malaysia voltage
Malaysia declares 230 V single-phase and 400 V three-phase at 50 Hz, with 11 kV and 33 kV distribution, following British-derived practice.
Japan
Japan is the only major market with two frequencies: 50 Hz in the east and 60 Hz in the west, both at 100 V for outlets and 200 V for three-phase. Equipment sold nationally must handle both frequencies.
For any Asian project, check whether the LV system is TN, TT or IT earthed, since that changes RCD and neutral requirements, as summarized in our voltage classes guide.
How to Specify a Transformer for a Foreign Grid
Country voltage data only becomes useful once it is turned into a transformer specification. Use this procedure for export or overseas projects.
- Confirm the primary voltage and BIL with the local utility: for example 11 kV with 75 kV BIL in a UK-derived network, or 13.8 kV with 95 kV BIL in a 60 Hz market.
- Confirm frequency. A 50 Hz design operated at 60 Hz has 17 percent lower flux at the same voltage and is usually acceptable; the reverse is not, because
B ∝ V / frises 20 percent. - Set the secondary voltage at no-load: 433 V for a 400 V Indian system, 415 V for many Commonwealth markets, 400 V in the EU, 480Y/277 V or 208Y/120 V in North America.
- Choose the vector group to match local practice: Dyn11 is typical in IEC markets; North American pad-mounts generally use delta-wye (30-degree angular displacement) or grounded wye-grounded wye (0-degree displacement).
- Specify taps and impedance to suit grid regulation and fault levels.
- Name the governing standard: IEC 60076, IEEE C57.12.00, GB 1094 or GOST, plus any national efficiency rule.
Worked example: a 1,000 kVA unit with a 20 kV primary and 400 V secondary carries 1,000,000 / (1.732 × 20,000) = 28.9 A on the HV side and 1,000,000 / (1.732 × 400) = 1,443 A on the LV side. Rerated for a 13.8 kV 60 Hz project with 480 V secondary, HV current is 41.8 A and LV current 1,203 A, which changes bushings, LV busbar and breaker frame. Our power distribution voltages article explains how these levels are chosen.
Next Steps: Specifying and Sourcing Equipment by Country
For multi-country projects, build a short grid data sheet for each site before issuing an RFQ: nominal LV and MV voltages, frequency, earthing system, fault level, utility metering and protection requirements, and the national standard or certification required.
- Avoid ordering "220 V" or "110 V" equipment; specify the exact nominal and tolerance.
- Specify dual-frequency rating only where the equipment genuinely needs to move between grids, since it can add cost.
- Ask for the routine test report at the site frequency and confirm tap settings before shipment.
MARS builds oil-immersed distribution transformers, dry-type units and compact transformer substations for 50 Hz and 60 Hz grids, designed to IEC 60076 with ANSI/IEEE, GB and GOST variants. Every unit receives routine tests, and FAT is welcome. Simple voltage conversions for imported equipment are compared in voltage converters and transformers. Send your site data via the quote request and we will return a matched specification.
Frequently asked questions
What is the voltage in the UK?
The UK declares 230 V single-phase and 400 V three-phase at 50 Hz, with a permitted range of 216.2 to 253 V. In practice many British networks still deliver close to 240 V because they were originally built for 240/415 V before European harmonization. Distribution transformers are typically fed at 11 kV.
What is the voltage in India?
India supplies 230 V single-phase and 400 V three-phase at 50 Hz, although 415 V is still commonly quoted for three-phase. Distribution is mainly at 11 kV and 33 kV, and distribution transformers usually have a 433 V no-load secondary so that loads receive about 400 to 415 V.
Is Canada 240V or 120V?
Canada is both. Homes receive 120/240 V split-phase at 60 Hz, with 120 V outlets and 240 V for heavy appliances. Many commercial and industrial buildings use 600Y/347 V three-phase, with dry-type transformers stepping down to 208Y/120 V for receptacles and small equipment.
What is the voltage and frequency in Europe?
Europe uses 230 V single-phase and 400 V three-phase at 50 Hz. EN 50160 requires the supply to stay within plus or minus 10 percent of 230 V for most of the time. Medium-voltage distribution is usually at 10 kV or 20 kV, depending on the country and utility.
What voltage does the Philippines use?
The Philippines uses 230 V, often still called 220 V, at 60 Hz. The 60 Hz frequency differs from most of Asia, so equipment designed only for 50 Hz should be checked. Distribution and earthing arrangements vary by utility, so confirm them with the local distributor before installation.
What is the difference between US and European voltage?
The US uses 120 V outlets and 240 V split-phase at 60 Hz, while Europe uses 230 V outlets and 400 V three-phase at 50 Hz. European circuits carry about half the current for the same power. Equipment moved between the two needs a voltage transformer and a frequency compatibility check.
Written and reviewed by the MARS application engineering team in Shanghai, who specify and test transformers, switchgear, substations and battery storage for projects in 40+ countries. Last updated .