Key takeaways
- Single-phase current equals kilowatts times 1,000 divided by voltage and power factor, so 5 kW at 240 V and unity power factor draws 20.8 A.
- Three-phase current divides by 1.732 times line-to-line voltage, so 22 kW at 400 V and unity power factor draws 31.8 A per phase.
- Power factor must be included for motors and drives; at PF 0.85 the current is about 18 percent higher than the unity power factor value.
- To convert amps to kW, reverse the formula: 200 A at 480 V three-phase and PF 0.85 equals about 141 kW of real power.
- Conductor and breaker sizing must use calculated amps plus the 125 percent continuous-load factor required by NEC 210.19 and 215.2.
Quick answer: To convert kW to amps, divide watts by voltage and power factor. Single-phase: I = kW × 1,000 / (V × PF). Three-phase: I = kW × 1,000 / (1.732 × V × PF). For example, 10 kW at 230 V single-phase and PF 1.0 draws 43.5 A, while 10 kW at 400 V three-phase and PF 0.85 draws 17.0 A.
Kilowatts describe how much real power a load uses; amps describe the current that cables, breakers, busbars and transformers must carry. Converting kW to current is the step that links a load schedule to every piece of hardware upstream of it, from a 16 A EV charger circuit to a 2,000 A switchboard incomer.
This guide gives the kilowatt to amps formulas for DC, single-phase and three-phase systems, a ready conversion table, the reverse amps to kW formulas and worked examples for common sizes. It is written for electrical designers, contractors and plant engineers who want a calculation they can defend in a design review.
How Do You Convert kW to Amps? The Three Formulas
A kilowatt is 1,000 watts of real power, the rate at which energy is converted to work or heat. An ampere is the unit of electric current. To convert kW to current you need the voltage, the system type and, for AC, the power factor.
| System | kW to amps formula | Amps to kW formula |
|---|---|---|
| DC | I = kW × 1,000 / V | kW = V × I / 1,000 |
| AC single-phase | I = kW × 1,000 / (V × PF) | kW = V × I × PF / 1,000 |
| AC three-phase (VLL) | I = kW × 1,000 / (√3 × VLL × PF) | kW = √3 × VLL × I × PF / 1,000 |
| AC three-phase (VLN) | I = kW × 1,000 / (3 × VLN × PF) | kW = 3 × VLN × I × PF / 1,000 |
√3 is 1.732. Use line-to-line voltage (400 V, 480 V, 208 V) with the √3 form, or line-to-neutral voltage (230 V, 277 V, 120 V) with the factor of 3. Both give the same answer because VLL = √3 × VLN.
Power factor is the ratio of real power to apparent power. Resistive heaters, ovens and incandescent lighting have PF close to 1.0. Induction motors typically run at 0.80 to 0.90 at full load, and much lower when lightly loaded. If you know kVA instead of kW, use the kVA form and skip PF; the relationship between the two is explained in our kVA vs kW guide.
If motor efficiency matters, remember that a motor's kW nameplate is shaft output. Electrical input is kWout / η, which is what drives current.
Kilowatts to Amps Conversion Table (kW to Amps Chart)
This kW to amps chart gives full-load current for common ratings. Single-phase columns assume PF 1.0 (resistive or PFC-corrected loads); three-phase columns assume PF 0.85, typical of motor-dominated loads, except where noted.
| kW | 230 V 1-ph | 240 V 1-ph | 400 V 3-ph PF 1.0 | 400 V 3-ph PF 0.85 | 480 V 3-ph PF 0.85 | 208 V 3-ph PF 0.85 |
|---|---|---|---|---|---|---|
| 1 kW | 4.3 A | 4.2 A | 1.4 A | 1.7 A | 1.4 A | 3.3 A |
| 5 kW | 21.7 A | 20.8 A | 7.2 A | 8.5 A | 7.1 A | 16.3 A |
| 8 kW | 34.8 A | 33.3 A | 11.5 A | 13.6 A | 11.3 A | 26.1 A |
| 9 kW | 39.1 A | 37.5 A | 13.0 A | 15.3 A | 12.7 A | 29.4 A |
| 10 kW | 43.5 A | 41.7 A | 14.4 A | 17.0 A | 14.2 A | 32.7 A |
| 11 kW | 47.8 A | 45.8 A | 15.9 A | 18.7 A | 15.6 A | 35.9 A |
| 20 kW | 87.0 A | 83.3 A | 28.9 A | 34.0 A | 28.3 A | 65.3 A |
| 22 kW | 95.7 A | 91.7 A | 31.8 A | 37.4 A | 31.1 A | 71.8 A |
| 50 kW | 217 A | 208 A | 72.2 A | 84.9 A | 70.8 A | 163 A |
| 100 kW | 435 A | 417 A | 144 A | 170 A | 142 A | 327 A |
A quick rule of thumb for 400 V three-phase motor loads: about 1.7 A per kW at PF 0.85. For 480 V, about 1.4 A per kW. For 230 V single-phase resistive loads, about 4.35 A per kW. Rules of thumb are fine for budget estimates but never for final protection settings.
For nameplate-based motor current rather than calculated values, use the tables in NEC Article 430 or the motor data sheet; see our full load amps calculator guide.
Worked Examples: 1 kW, 10 kW, 11 kW and 22 kW to Amps
These worked examples cover the sizes people search for most, including EV charging, which publishes power in kW but is wired in amps.
1 kW to amps at 230 V
I = 1,000 / (230 × 1.0) = 4.35 A. A 1 kW kettle element draws about 4.3 A in Europe and 8.3 A on a 120 V US circuit.
10 kW to amps, single-phase 240 V
I = 10,000 / 240 = 41.7 A. A 10 kW electric water heater on US split-phase is a continuous load, so the circuit needs 41.7 × 1.25 = 52 A of conductor ampacity per NEC 422.13 and 210.19, leading to a 60 A breaker with 6 AWG copper.
11 kW to amps, three-phase 400 V
Wallbox chargers rated 11 kW draw 11,000 / (1.732 × 400 × 1.0) = 15.9 A per phase, which is why they are wired on 16 A three-phase circuits in Europe.
22 kW to amps, three-phase 400 V
I = 22,000 / (1.732 × 400) = 31.8 A, served by a 32 A three-phase circuit. The same 22 kW on a 230 V single-phase supply would need 95.7 A, beyond most residential services, which is why 22 kW chargers require three-phase supply.
50 kW motor load at 480 V
A 50 kW conveyor drive at PF 0.85 and 93 percent efficiency draws 50,000 / (1.732 × 480 × 0.85 × 0.93) = 76.1 A. Ignoring efficiency underestimates current by 7 percent. If the load is specified in horsepower, convert first with our hp to kVA and kW guide.
Amps to kW Formula: How to Figure kW from Amps
Going from current to power is common when auditing an existing installation: you know the breaker or measured amps and need to know how many kilowatts the circuit is supplying.
- Measure or read the RMS line current with a true-RMS clamp meter on each phase.
- Measure line-to-line voltage (three-phase) or line-to-neutral voltage (single-phase) at the same point.
- Obtain the power factor from a power analyzer or the equipment data; if unknown, use 0.85 for motor loads and 1.0 for resistive loads as an estimate.
- Apply
kW = √3 × V × I × PF / 1,000for three-phase orkW = V × I × PF / 1,000for single-phase. - Average the three phase currents if they differ by less than 10 percent; if imbalance is larger, calculate each phase separately using line-to-neutral voltage and sum.
200 amps to kW: a 200 A, 240 V single-phase service at PF 1.0 represents 240 × 200 / 1,000 = 48 kW. A 200 A feeder at 480 V three-phase and PF 0.85 carries 1.732 × 480 × 200 × 0.85 / 1,000 = 141 kW. At 208 V three-phase the same 200 A is only 61 kW, a vivid illustration of why higher distribution voltages save copper.
20 amps to kW: a 20 A, 120 V branch circuit at PF 1.0 supplies 2.4 kW; at 230 V it supplies 4.6 kW. Remember that continuous loads are limited to 80 percent of the breaker rating, so practical continuous capacity is 1.92 kW and 3.68 kW.
For three-phase power calculations with unbalanced loads, see the 3-phase calculator guide.
kW Calculation for 3-Phase Systems: Balanced and Unbalanced Loads
The √3 formula assumes balanced loading, with equal current in each phase. Real installations, especially those mixing single-phase loads on a three-phase four-wire supply, are rarely perfectly balanced.
For unbalanced systems, calculate each phase separately:
Ptotal = VAN × IA × PFA + VBN × IB × PFB + VCN × IC × PFC
Example: a 400/230 V board measures 62 A, 48 A and 55 A on phases A, B and C, with an overall PF of 0.9. Total real power is 230 × (62 + 48 + 55) × 0.9 / 1,000 = 34.2 kW. Using the balanced formula with average current (55 A) gives 1.732 × 400 × 55 × 0.9 / 1,000 = 34.3 kW, close enough for loading checks, but the conductor and breaker must still be sized for the 62 A worst phase.
The neutral carries the phasor sum of the phase currents. With balanced linear loads that sum is zero. With unbalance or triplen harmonics from LED drivers and IT equipment, the neutral can approach or exceed phase current, which is why IEC 60364-5-52 and NEC 310.15 require harmonic adjustment.
The same formulas size the upstream transformer. A building with 680 kW of demand at PF 0.88 needs 680 / 0.88 = 773 kVA, so an 800 kVA or 1,000 kVA unit depending on growth. Our transformer kVA sizing guide covers diversity and future margin.
From kW and Amps to Cable, Breaker and kWh
Once current is known, the hardware follows. A short sequence keeps the result safe and code-compliant.
- Continuous loads: loads running three hours or more need conductors and overcurrent devices rated at 125 percent of continuous current under NEC 210.19, 210.20 and 215.2.
- Conductor ampacity: select from NEC Table 310.16 or IEC 60364-5-52, then apply correction for ambient temperature and grouping.
- Voltage drop: keep feeders plus branch circuits under about 5 percent total; long runs often push conductor size up one or two steps. See the wire size calculator guide.
- Breaker: choose the next standard rating at or above the adjusted current, coordinated with the conductor.
Amps and kWh: kilowatts are power; kilowatt-hours are energy. A battery's energy in kWh is Ah × V / 1,000, so a 280 Ah cell string at 51.2 V nominal stores 14.3 kWh. Running a 10 kW load from it draws 10,000 / 51.2 = 195 A DC, for about 1.4 hours ignoring inverter losses. An ampere-kWh calculator is simply these two formulas combined.
For the full current calculation methods behind transformer ratings, read transformer current calculation formulas.
Common Mistakes When Converting Kilowatts to Amps
Most errors in kW to amps conversion come from a handful of avoidable slips.
- Using line-to-neutral voltage with √3. 10 kW / (1.732 × 230) gives 25.1 A, nearly double the correct 14.4 A at 400 V.
- Ignoring power factor. Treating a 0.8 PF motor load as PF 1.0 underestimates current by 20 percent; the real current is 25 percent higher than the estimate.
- Confusing kW with kVA. Generators and transformers are rated in kVA; dividing kVA by PF again double counts.
- Using motor output instead of input. Nameplate kW is mechanical output; divide by efficiency for electrical input.
- Forgetting starting current. Direct-on-line motors draw 6 to 8 times running current for several seconds, which affects transformer and generator sizing even though it does not change conductor ampacity.
- Applying European voltage to US equipment or the reverse. Always use the actual system nominal.
A kW calculator or kW amp calculator is only as good as its inputs. Write the voltage, phase count, PF and efficiency next to every result in your load schedule so reviewers can check it.
Next Steps: Specifying and Sourcing from Your Load Current
Once the load schedule is converted to amps and kVA, specify the supply equipment with the same data so the manufacturer can confirm ratings.
- Provide total demand in kW and kVA, power factor and the largest motor's starting kVA.
- State system voltage, phase arrangement and frequency, plus fault level at the point of supply.
- Request full-load current, impedance and losses on the transformer data sheet, and incomer and busbar ratings on the switchgear.
MARS supplies oil-immersed distribution transformers from small kVA ratings up to power transformers of 31,500 kVA, along with IEC 61439 low-voltage boards on the HV and LV switchgear hub. Check sizing with the transformer sizing calculator and send the load list through the quote request.
Frequently asked questions
How many amps is 10 kW?
10 kW draws 43.5 A at 230 V single-phase or 41.7 A at 240 V, assuming unity power factor. On a 400 V three-phase supply it draws 14.4 A at PF 1.0 or 17.0 A at PF 0.85. At 480 V three-phase and PF 0.85 the current is about 14.2 A.
How do you convert kW to amps in three-phase?
Multiply kW by 1,000 and divide by 1.732 times the line-to-line voltage times the power factor. For 30 kW at 400 V and PF 0.9, current is 30,000 divided by (1.732 x 400 x 0.9), which equals 48.1 A per phase. Use line-to-line, not line-to-neutral, voltage.
How many amps is 22 kW?
22 kW on a 400 V three-phase supply at unity power factor draws 31.8 A per phase, which is why 22 kW EV chargers use 32 A three-phase circuits. The same power on a 230 V single-phase supply would need 95.7 A, which exceeds most residential service capacity.
How do I convert amps to kW?
For single-phase, multiply volts by amps by power factor and divide by 1,000. For three-phase, multiply 1.732 by line-to-line volts, amps and power factor, then divide by 1,000. For example, 100 A at 400 V three-phase and PF 0.85 equals 58.9 kW.
How many kW is 200 amps?
A 200 A single-phase 240 V service corresponds to 48 kW at unity power factor. At 480 V three-phase and PF 0.85, 200 A equals about 141 kW. At 400 V three-phase and PF 0.85 it equals about 118 kW. Continuous loading should not exceed 80 percent of the breaker rating.
How many amps is 5 kW?
5 kW draws 21.7 A at 230 V and 20.8 A at 240 V single-phase, or 41.7 A at 120 V. On a 400 V three-phase supply, 5 kW draws 7.2 A at unity power factor and 8.5 A at PF 0.85.
Written and reviewed by the MARS application engineering team in Shanghai, who specify and test transformers, switchgear, substations and battery storage for projects in 40+ countries. Last updated .
Tags: kw to amps kilowatt amps kw to amps chart amps to kw formula kw calculation for 3 phase