Key takeaways
- Apparent power S = V × I in single phase and √3 × V_L × I_L in three phase; it is measured in VA, kVA or MVA.
- Real power P = S × cos φ in watts does work; reactive power Q = S × sin φ in var sustains magnetic and electric fields.
- Complex power S = V × I* = P + jQ, so loads are summed by adding P and Q separately, never by adding kVA magnitudes.
- A 480 V three-phase load drawing 150 A at 0.82 PF takes 124.7 kVA, 102.3 kW and 71.4 kvar.
- Transformers are rated in kVA per IEC 60076-1 and IEEE C57.12.00 because winding heating depends on current, whatever the power factor.
Quick answer: The apparent power formula is S = V × I for single phase and S = √3 × V_L × I_L for three phase, measured in volt-amperes (VA or kVA). Apparent power combines real power P (watts) and reactive power Q (var) as S = √(P² + Q²), with P = S × cos φ and Q = S × sin φ. Transformers and cables are sized on S.
AC power comes in three forms that engineers handle every day: apparent power, which sets the current and therefore the size of transformers, cables and switchgear; real power, which turns into heat, motion and light; and reactive power, which circulates to build magnetic and electric fields. Mixing them up leads to undersized transformers, wrong breaker settings and confusing utility bills.
This guide is for design engineers, students and electrical estimators who need the formulas and their application. It covers single-phase and three-phase equations, units, complex power, worked examples from impedance and from nameplate data, and the correct way to add mixed loads when sizing a transformer.
What Are the Types of Electrical Power?
In an AC circuit with voltage and current out of phase, instantaneous power p(t) = v(t) × i(t) pulsates at twice the supply frequency and becomes negative for part of each cycle when reactive elements return stored energy. Averaging and decomposing that waveform gives three quantities.
- Real power (P), also called true or active power, is the average rate of energy conversion into work or heat, measured in watts (W).
- Reactive power (Q) is the amplitude of the energy exchange between source and the fields of inductors and capacitors, measured in volt-amperes reactive (var). It averages to zero energy over a cycle.
- Apparent power (S) is the product of RMS voltage and RMS current, measured in volt-amperes (VA). It is what the source and conductors must carry.
| Quantity | Symbol | Unit | Single phase | Three phase (balanced) |
|---|---|---|---|---|
| Apparent power | S | VA, kVA, MVA | V × I | √3 × V_L × I_L |
| Real power | P | W, kW, MW | V × I × cos φ | √3 × V_L × I_L × cos φ |
| Reactive power | Q | var, kvar, Mvar | V × I × sin φ | √3 × V_L × I_L × sin φ |
| Power factor | PF | none | P / S | P / S |
The ratio P/S is the power factor, treated in depth, including correction and harmonics, in power factor explained. Here the focus is on calculating each quantity.
Apparent Power Formula and Equation
Apparent power is measured in volt-amperes because it is literally RMS volts multiplied by RMS amperes, without regard to phase angle. The apparent power equation can be written in several equivalent forms:
S = V × I(from voltage and current)S = I² × Z(from current and impedance magnitude)S = V² / Z(from voltage and impedance magnitude)S = √(P² + Q²)(from real and reactive power)S = P / PF(from real power and power factor)
How to find apparent power: single-phase example
A 240 V circuit feeds a load with resistance 8 Ω and inductive reactance 6 Ω.
Z = √(8² + 6²) = 10 ΩI = 240 / 10 = 24 AS = 240 × 24 = 5,760 VAP = I² × R = 24² × 8 = 4,608 WQ = I² × X = 24² × 6 = 3,456 var- Check:
√(4,608² + 3,456²) = 5,760 VA; PF = 4,608 / 5,760 = 0.80
The example shows why VA and W differ on nameplates: the resistor converts 4.6 kW to heat while the supply carries 5.76 kVA. The relationship between nameplate VA and watts is also discussed in volt-ampere vs watts.
When only voltage and current are known, apparent power is always calculable; real and reactive power additionally require the phase angle or a power meter.
Three Phase Apparent Power Formula and Calculation
For a balanced three-phase system, total apparent power is three times the per-phase value. In a wye connection each phase carries line current at phase voltage V_L / √3, so S = 3 × (V_L / √3) × I_L = √3 × V_L × I_L. A delta connection reaches the same result with line voltage and I_L / √3 per winding.
Apparent power calculation, 3 phase example
A 480 V three-phase motor control center draws 150 A at 0.82 PF lagging.
S = 1.732 × 480 × 150 = 124.7 kVAP = 124.7 × 0.82 = 102.3 kWsin φ = √(1 − 0.82²) = 0.572Q = 124.7 × 0.572 = 71.4 kvar- Check:
√(102.3² + 71.4²) = 124.7 kVA
Unbalanced loads
If phase currents differ, calculate per phase and sum: S = V_an × I_a + V_bn × I_b + V_cn × I_c for apparent power magnitude on a four-wire system, and sum P and Q separately per phase for exact results. The √3 shortcut assumes balance.
Converting kVA back to line current is the most common use of the formula on site: I_L = S / (√3 × V_L). A 500 kVA transformer at 400 V delivers 500,000 / (1.732 × 400) = 722 A. Further current tables are in the 3 phase calculator guide.
Real Power Equation: How to Calculate True Power
True power is the energy actually delivered per second. The real power equation for any waveform is the average of instantaneous power over one period, P = (1/T) ∫ v(t) × i(t) dt. For sinusoidal quantities this reduces to the familiar true power equation P = V × I × cos φ, or √3 × V_L × I_L × cos φ in three phase.
Because only resistance dissipates energy, real power can also be found as P = I² × R, using the resistive part of the load impedance, or from voltage across the resistive element only.
Methods to calculate true power
- From a wattmeter: direct reading, the most reliable for distorted waveforms.
- From V, I and PF: requires a power factor measurement or known load PF.
- From impedance:
P = I² × R, useful in equivalent-circuit calculations. - From energy: average P = kWh / hours over a metering interval.
- Two-wattmeter method: on three-wire three-phase circuits,
P = W₁ + W₂andQ = √3 × (W₂ − W₁), which gives reactive power too.
Example: two-wattmeter readings
On a three-wire 400 V circuit, W₁ = 18 kW and W₂ = 32 kW. P = 50 kW; Q = 1.732 × 14 = 24.2 kvar; S = √(50² + 24.2²) = 55.6 kVA; PF = 0.90.
Real power is what motors convert to shaft output divided by efficiency, so motor input kW is P_out / η; conversions between hp, kW and kVA are covered in hp to kVA and kW conversion.
Reactive Power Formula in 3 Phase and Reactance Power
Reactive power is associated with reactance. In a single reactive element, the reactance power formula is Q = I² × X = V_X² / X, with inductive reactance X_L = 2πfL and capacitive reactance X_C = 1 / (2πfC). By convention inductive Q is positive (absorbed) and capacitive Q is negative (supplied).
The reactive power formula in 3 phase is Q = √3 × V_L × I_L × sin φ, or for a balanced bank of three reactive elements, Q = 3 × V_ph² / X.
Worked example: three-phase capacitor bank
A wye-connected bank of 3 × 200 µF on a 400 V, 50 Hz system. Phase voltage 231 V. X_C = 1 / (2π × 50 × 200 × 10⁻⁶) = 15.9 Ω. Q = 3 × 231² / 15.9 = 10.1 kvar. Connected in delta, each capacitor sees 400 V, giving 3 × 400² / 15.9 = 30.2 kvar, three times as much.
Where reactive power comes from and goes
| Element | Q behavior | Typical magnitude |
|---|---|---|
| Induction motors | Absorb, mostly magnetizing | Large share of site kvar |
| Transformers | Absorb: magnetizing plus I²X leakage | Leakage Q at full load ≈ %X × rated kVA |
| Overhead lines | Absorb under load, supply at light load | Depends on loading vs surge impedance load |
| Cables | Supply, due to capacitance | Significant at MV and HV |
| Capacitor banks | Supply | Sized for correction |
| Synchronous machines and inverters | Either, controllable | Within capability curve |
A 1,000 kVA transformer with 6% reactance absorbs roughly 60 kvar in leakage reactance at full load, a useful figure when balancing site reactive demand.
Power Formula for AC Current: Complex Power
The most compact power formula for AC current uses phasors. Complex power is S = V × I* = P + jQ, where I* is the complex conjugate of the current phasor. The magnitude |S| is apparent power, the real part is P and the imaginary part is Q.
Example: V = 230∠0° V and I = 20∠−30° A. Then I* = 20∠+30° and S = 230 × 20 ∠30° = 4,600∠30° VA = 3,984 W + j2,300 var. The positive Q confirms an inductive, lagging load.
Complex notation matters because it makes summation rigorous. Power from several loads on the same bus adds as complex numbers: real parts together, imaginary parts together. Adding kVA magnitudes overstates the total whenever the loads have different power factors.
A fourth quantity appears when harmonics are present: distortion power D, defined so that S² = P² + Q² + D². Harmonic currents increase apparent power and conductor heating without contributing to P or fundamental Q. This is why transformers supplying large drive or data center loads are specified with a harmonic profile or K-factor; see kVA vs kW for the rating implications.
Using Apparent Power to Size a Transformer
Transformers are rated in kVA, not kW. IEC 60076-1 and IEEE C57.12.00 define rated power as apparent power, because winding temperature depends on current and core temperature on voltage, neither of which depends on power factor. The same 1,000 kVA unit delivers 1,000 kW at unity PF or 800 kW at 0.8 PF with identical heating.
Worked example: summing mixed loads
| Load | Data | P (kW) | Q (kvar) | S (kVA) |
|---|---|---|---|---|
| A: motors | 100 kW at 0.80 PF | 100 | 75 | 125 |
| B: heaters | 60 kW at 1.00 PF | 60 | 0 | 60 |
| C: welders | 50 kVA at 0.60 PF | 30 | 40 | 50 |
| Total | Vector sum | 190 | 115 | 222 |
Total S = √(190² + 115²) = 222 kVA, compared with 235 kVA if the kVA column is simply added. With 20% growth allowance, 266 kVA is required, so a 300 kVA transformer is a reasonable selection; a 250 kVA unit would run above nameplate if growth materializes. Demand and diversity factors should be applied to each load before summation where they are known.
For the full procedure, including diversity and motor starting, see the transformer kVA sizing guide or run the numbers in the transformer sizing calculator. Methods for deriving kVA from existing installations are in how to determine kVA.
Next Steps: Specifying and Sourcing
When apparent power calculations lead to a transformer or substation purchase, translate them into a clear specification:
- Rated kVA based on the vector sum of loads, with stated diversity and growth margin.
- Expected PF and harmonic content, so load losses and neutral current can be designed for.
- Primary and secondary voltages, vector group and tap range.
- Cooling class and any future fan-cooled rating (for example ONAN/ONAF) to cover peak kVA.
- Percent impedance, which sets short-circuit current and reactive power absorbed at full load.
- Design standard and frequency: IEC 60076 or IEEE C57.12.00, 50 or 60 Hz.
MARS manufactures oil-immersed transformers from distribution ratings up to 31,500 kVA power transformers, and dry-type transformers for indoor sites, all routine tested before dispatch. Share your load list on the quotation page for a sized and priced proposal.
Frequently asked questions
What is the formula for apparent power?
Apparent power S equals RMS voltage times RMS current: S = V × I for single phase and S = √3 × V_L × I_L for balanced three phase. It can also be calculated as S = √(P² + Q²) from real and reactive power, or S = P / PF from real power and power factor.
What is apparent power measured in?
Apparent power is measured in volt-amperes (VA), with kilovolt-amperes (kVA) and megavolt-amperes (MVA) for larger equipment. VA is used instead of watts to signal that the figure includes both real and reactive components. Transformers, UPS units and generators are commonly rated in kVA.
How do you calculate reactive power in a 3 phase system?
Use Q = √3 × V_L × I_L × sin φ, where φ is the angle whose cosine is the power factor. A 400 V load drawing 100 A at 0.8 PF has sin φ = 0.6, so Q = 1.732 × 400 × 100 × 0.6 = 41.6 kvar. Alternatively, Q = √(S² − P²) from measured kVA and kW.
How do you calculate true power?
True power P = V × I × cos φ in single phase or √3 × V_L × I_L × cos φ in three phase. It can also be found as I² × R using the load's resistance, or measured directly with a wattmeter. With distorted waveforms, only a true-RMS power meter gives an accurate value.
Why are transformers rated in kVA instead of kW?
Transformer heating depends on winding current and core voltage, not on the power factor of the load. A manufacturer cannot know the customer's power factor, so rating in kVA defines capacity independent of load type. The kW a transformer delivers equals its kVA multiplied by the load power factor.
Can you add kVA values from different loads?
Only as an approximation that overstates the total. Correct summation adds real power and reactive power separately, then calculates S = √(ΣP² + ΣQ²). Simply adding kVA is acceptable when loads share a similar power factor, but it can oversize a transformer when loads are mixed.
Written and reviewed by the MARS application engineering team in Shanghai, who specify and test transformers, switchgear, substations and battery storage for projects in 40+ countries. Last updated .
Tags: apparent power formula apparent power equation three phase apparent power formula reactive power formula in 3 phase true power equation