240 to 480 Step Up Transformer: Sizing, Wiring & Options

240 to 480 step up transformer with open enclosure installed beside machine shop equipment

Key takeaways

  • A 240 to 480 step up transformer doubles voltage with a 1:2 turns ratio, so primary current is twice the secondary current for the same kVA.
  • Three-phase load current at 480 V is I = kVA × 1000 / (√3 × 480); a 75 kVA unit delivers about 90 A at 480 V and draws about 180 A at 240 V.
  • Reverse-feeding a standard 480-240 V unit is usually acceptable above about 3 kVA, but inrush rises and any wye neutral on the input side must stay unconnected.
  • NEC 450.3(B) limits primary-only protection to 125% of rated primary current, with up to 250% allowed when secondary protection is set at 125%.
  • Motor loads drive sizing: keep the starting voltage dip below roughly 10–15%, which often pushes a 50 hp motor from a 75 kVA to a 112.5 kVA transformer.

Quick answer: A 240 to 480 step up transformer raises a 240 V supply to 480 V with a 1:2 turns ratio so 480 V equipment can run on a 240 V service. For three-phase loads, size it as kVA = √3 × 480 × I / 1000 plus margin for motor starting, and choose a purpose-built step-up unit or a reverse-fed isolation transformer rated for back-feed.

Many machine tools, chillers, compressors and imported production lines are built for 480 V three-phase, while the building they land in has a 240 V service. Instead of re-engineering the machine or paying for a new utility service, the usual fix is a 240v to 480v step up transformer installed close to the load. Done properly it is a simple, efficient and long-lived solution; done carelessly it trips breakers at energization, overheats or leaves the 480 V side without a proper ground reference.

This guide is for plant engineers, electrical contractors and equipment buyers who need to size, wire and protect a step up transformer 240v to 480v 3 phase, or a single-phase variant.

What Is a 240 to 480 Step Up Transformer?

A step up transformer is a transformer whose secondary (output) voltage is higher than its primary (input) voltage, achieved by giving the secondary winding more turns than the primary. A 240 to 480 step up transformer has a nominal 1:2 ratio: every volt on the 240 V winding produces two volts on the 480 V winding, while current scales the opposite way.

The governing relationships are the ideal transformer equations:

  • V2 / V1 = N2 / N1 = 480 / 240 = 2
  • I1 = I2 × (N2 / N1) = 2 × I2
  • kVA1 ≈ kVA2 (minus losses of typically 1.5–3% for low-voltage dry-type units)

For a general introduction to how ratio, flux and windings interact, see our step-up transformer engineering guide.

Typical uses are running 460 V motors, compressors and imported machine tools in a facility with only 240 V service, or feeding a 480 V sub-board where only 240 V capacity is spare.

Most units in this range are ventilated or encapsulated low-voltage dry-type transformers built to NEMA ST 20, IEEE C57.12.01 and UL 1561 in North America, or IEC 60076-11 elsewhere, from about 3 kVA to 500 kVA.

Step Up Transformer 240V to 480V 3 Phase: Configurations Compared

The primary configuration must match the 240 V system you actually have. In North America 240 V three-phase is usually a three-wire delta, sometimes a high-leg (four-wire) delta, while 240 V single-phase is a 120/240 V split-phase service. The output configuration depends on whether the 480 V loads need a neutral.

ConfigurationInputOutputNeutral availableTypical use
240 Δ – 480Y/277240 V 3-wire delta480 V 3-phase 4-wireYes (277 V)Mixed motor + 277 V lighting loads
240 Δ – 480 Δ240 V 3-wire delta480 V 3-phase 3-wireNoMotor-only, machine tools
Reverse-fed 480 Δ – 240 Δ240 V delta480 V deltaNoRetrofit using a standard catalog unit
Single-phase 240 – 480240 V 2-wire480 V 2-wireNoSingle-phase heaters, small machines
Autotransformer 240 – 480240 V480 VShared windingCompact, no isolation required

A purpose-built 240 Δ – 480Y/277 unit is the cleanest solution: the delta primary blocks triplen harmonics from circulating back into the 240 V service, and the wye secondary creates a new separately derived system with a neutral that can be bonded and grounded per NEC 250.30. If your site has a high-leg delta, connect the transformer only to the three phase conductors; the high leg itself is not a problem for a delta primary. Our high-leg delta transformer guide explains that system in more detail.

If the 480 V system may ever be paralleled with another source, specify the phase displacement (for example Dyn1 or Dyn11); the vector group explainer covers how to read these codes.

Can You Reverse-Feed a 480 to 240 Transformer?

Reverse feeding means connecting the supply to the winding normally marked as the secondary (X terminals) so that a standard step-down unit works as a step up transformer. Many contractors do this because 480-240 V units are stock items. It works, but there are four conditions to check.

  1. Size above about 3 kVA. Small single-phase units often have compensated windings, meaning the low-voltage winding has a few percent extra turns to offset regulation. Reverse-fed, the output then sits several percent below 480 V. Larger units normally have an exact ratio.
  2. Higher inrush. The low-voltage winding is usually wound closest to the core. Energizing it produces higher magnetizing inrush, commonly 10–25 times rated current for a few cycles instead of 8–12 times. Primary breakers need a high instantaneous setting or time-delay fuses; see our transformer inrush current guide.
  3. No neutral connection on the input wye. If you reverse-feed a delta-wye unit by supplying the wye side, leave X0 unconnected to the supply neutral. A grounded wye input with a delta output forms a ground source that feeds faults elsewhere on the 240 V system.
  4. Taps move to the output. Taps are on the 480 V winding, so they now adjust output voltage directly. That is often convenient, but label them clearly.

Always confirm with the transformer manufacturer that the unit is suitable for back-feeding and that its nameplate and listing allow it. A purpose-wound step up unit avoids all four compromises and is usually preferred for new installations.

How to Size a 240 to 480 Volt Step Up Transformer

Size from the 480 V load, then check the 240 V supply can deliver twice the current. The three-phase formulas are:

  • kVA = √3 × V × I / 1000
  • I(480) = kVA × 1000 / (√3 × 480)
  • I(240) = kVA × 1000 / (√3 × 240)

For single-phase, drop the √3. Add 20–25% margin for future load and continuous operation, then round up to the next standard rating. Our standard transformer sizes list and the transformer sizing calculator make the rounding quick.

Rating (kVA)480 V current (A)240 V current (A)Approx. motor load at 460 V
1518.036.1Up to 7.5 hp
3036.172.2Up to 15 hp
4554.1108.3Up to 20–25 hp
7590.2180.4Up to 30–40 hp
112.5135.3270.6Up to 50–60 hp
150180.4360.8Up to 75 hp
225270.6541.3Up to 100–125 hp

The motor column is indicative and assumes across-the-line starting of a single largest motor with normal starting duty. Also check harmonic content: if the 480 V load is mostly drives or rectifiers, consider a K-rated design as described in our K-factor transformer guide.

Finally, confirm the 240 V service has spare capacity for twice the 480 V current.

Worked Example: Sizing for a 50 hp Motor

A workshop has a 240 V three-phase delta service and must run a new 50 hp, 460 V compressor started across-the-line, plus 5 kVA of 480 V auxiliary load.

Step 1: running load

NEC Table 430.250 gives 65 A full-load current for a 50 hp, 460 V motor. Running kVA is √3 × 480 × 65 / 1000 = 54.0 kVA. Adding 5 kVA auxiliary gives 59 kVA, so 75 kVA looks adequate on running load alone.

Step 2: starting voltage dip

A code letter G motor draws roughly 5.6–6.3 kVA per hp locked-rotor, so starting kVA is about 50 × 6.0 = 300 kVA. Treating the transformer as the dominant impedance (Z = 5%), its short-circuit capacity is kVA / Z:

  • 75 kVA: 75 / 0.05 = 1,500 kVA; dip ≈ 300 / (300 + 1,500) = 16.7%
  • 112.5 kVA: 112.5 / 0.05 = 2,250 kVA; dip ≈ 300 / 2,550 = 11.8%
  • 150 kVA: 150 / 0.05 = 3,000 kVA; dip ≈ 300 / 3,300 = 9.1%

A 16.7% dip will likely drop out contactors and may stall the start. The 112.5 kVA unit keeps the dip near 12%, acceptable for most compressors. If the 240 V service itself is weak, its impedance adds to the dip, so 150 kVA or a soft starter becomes the safer choice.

Step 3: primary current

At 112.5 kVA the 240 V side draws 271 A at full load. With secondary protection at 125% (about 169 A, so a 175 A breaker), NEC 450.3(B) permits primary protection up to 250% of 271 A. A 400 A primary breaker with an adjustable instantaneous trip rides through inrush comfortably. Size feeder conductors to the breaker and to NEC 215 and 240.21(C) for the secondary tap.

Wiring, Grounding and Overcurrent Protection

A transformer with isolated windings creates a separately derived system, so the 480 V side needs its own bonding and grounding even though the 240 V side is already grounded. Follow this sequence and have the installation inspected and performed by qualified electricians under local code.

  1. Mount the transformer with the clearances shown on its nameplate drawing; ventilated units need free air at the openings and must not be enclosed with other heat sources.
  2. Connect the 240 V feeder to the 240 V winding terminals marked on the nameplate (the X terminals on a reverse-fed standard unit) through a primary breaker or fused disconnect sized per NEC 450.3(B).
  3. Bring the equipment grounding conductor to the enclosure ground bus; size it per NEC Table 250.122 for the primary overcurrent device.
  4. For a wye output, install the system bonding jumper between the secondary neutral terminal and the enclosure at one point only, and connect a grounding electrode conductor per NEC 250.30 and Table 250.66.
  5. Run 480 V secondary conductors to a secondary breaker or panel within the tap-length limits of NEC 240.21(C).
  6. Before energizing, measure insulation resistance between windings and to ground, verify tap position and check phase rotation on the 480 V side.

For a 480 V delta output with no neutral, NEC 250.21 and 250.26 still require a decision on grounding: either corner-grounding, a high-resistance grounding scheme or an ungrounded system with ground detectors. Fuse and breaker selection is covered in our transformer fuse sizing guide.

240 to 480 Transformer vs Autotransformer vs Phase Converter

Three devices get confused in searches for a 240 to 480 phase converter or transformer. They solve different problems.

DeviceChanges voltageCreates 3-phase from 1-phaseIsolationPhysical size
Isolation step up transformerYes (240 → 480)NoYesFull kVA
Step up autotransformerYesNoNoAbout 50% of load kVA for 2:1
Rotary or static phase converterNo (240 → 240)YesNoSized by motor hp
Phase converter + step up transformerYesYesYes (via transformer)Two devices

An autotransformer uses one shared winding. For a 2:1 ratio the series portion carries only half the power, so its equivalent two-winding rating is kVA × (1 − 240/480) = 0.5 × kVA. It is lighter but provides no isolation. Our autotransformer guide explains the trade-offs.

If the site only has 240 V single-phase, a transformer alone cannot produce three phases. You need a phase converter or a single-phase-input drive to create 240 V three-phase first, then a step up transformer to reach 480 V. A drive fed from 240 V cannot output 480 V on its own because its DC bus is set by the input. See our single phase to 3 phase converter guide for those options, and our 208 to 480 transformer guide if your service is actually 208Y/120 V.

Next Steps: Specifying and Sourcing

A clear specification gets you an accurate quote and a transformer that energizes first time. Include these items in your RFQ:

  • Rating in kVA and phase count, with the load list (largest motor hp, starting method, harmonic loads).
  • Primary voltage and system type (240 V delta, high-leg delta or 120/240 V single-phase) and secondary voltage (480 V delta or 480Y/277 V).
  • Frequency (60 Hz, or 50 Hz for export equipment), impedance target and tap range (commonly ±2 × 2.5%).
  • Insulation system and temperature rise (for example 220 °C system with 150 °C, 115 °C or 80 °C rise), enclosure type (NEMA 1, NEMA 3R or IP rating) and installation altitude.
  • Efficiency requirement (US DOE 10 CFR 431 for low-voltage dry-type units sold in the US), standards (IEEE C57.12.01, UL 1561 or IEC 60076-11) and test reports required.
  • Whether the unit will be reverse-fed, so the manufacturer can confirm suitability.

MARS designs and builds cast-resin and ventilated dry-type transformers for step-up and step-down duty at 50 and 60 Hz, with ANSI/IEEE and IEC variants, routine tests on every unit and a typical 25–45 day lead time. If the 480 V output feeds a new distribution board, our LV switchgear can be quoted in the same package. Send your load list and voltages through the quote request form and an engineer will confirm sizing before pricing.

Frequently asked questions

Can I use a 480 to 240 transformer backwards to step up 240 to 480?

Usually yes for units above about 3 kVA, provided the manufacturer approves back-feeding. Expect higher inrush current, leave any wye neutral on the input side unconnected, and note that taps now adjust the output. Small units with compensated windings will produce a few percent less than 480 V when reverse-fed.

What size transformer do I need to step up 240V to 480V for a 30 hp motor?

A 30 hp, 460 V motor draws about 40 A, or roughly 33 kVA running. For across-the-line starting, 75 kVA is a common choice because it keeps the starting dip near 11% with 5% impedance; a 45 kVA unit would dip about 17%. A soft starter or reduced-voltage start can allow 45 kVA.

How many amps does a 75 kVA 240 to 480 transformer draw?

At full load a three-phase 75 kVA unit draws 75,000 / (1.732 × 240) ≈ 180 A on the 240 V side and delivers about 90 A at 480 V. Add roughly 2% for losses, and allow for inrush when energizing, which can reach 10 to 25 times rated current for a few cycles.

Is a 240 to 480 phase converter the same as a step up transformer?

No. A phase converter creates three-phase power from a single-phase supply but keeps the same voltage. A step up transformer changes voltage but cannot create extra phases. To run a 480 V three-phase machine from 240 V single-phase you need both: a converter to make 240 V three-phase, then a step up transformer to 480 V.

Do I need a neutral on the 480V side?

Only if you have 277 V loads such as lighting or single-phase equipment. Motor-only loads run on a three-wire 480 V delta. If you choose a 480Y/277 V secondary, bond the secondary neutral to ground at the transformer or first disconnect and install a grounding electrode conductor, as required for a separately derived system.

Written and reviewed by the MARS application engineering team in Shanghai, who specify and test transformers, switchgear, substations and battery storage for projects in 40+ countries. Last updated .